730 kVA diesel generators.
Compare UK-designed and UK-manufactured 730 kVA diesel generator options and nearby ratings from Baudouin, Perkins, Scania. Check the exact prime and standby output, engine and enclosure before selecting.
Options around 730 kVA.
A rounded GPS model class is not a guaranteed duty rating. The tables below identify the actual documented output for each reference configuration.
Specify 730 kVA around your load.
Consider installation access, load steps, future expansion and the control interface alongside the rating. Synchronisation, changeover and acoustic requirements need a project-specific specification.
At a power factor of 0.8, 730 kVA corresponds to 584 kW mathematically. That conversion is not a substitute for the manufacturer’s duty rating or a starting-load assessment.
Discuss your load scheduleDoes a 730 kVA model deliver 730 kVA continuously?
The model class alone does not establish continuous capability. Check prime and standby ratings and the manufacturer’s load-profile conditions. Confirm the intended run hours and average load when requesting a quotation.
Can I get a canopied 730 kVA generator?
Compare the canopied entries above, then confirm enclosure dimensions, sound requirements and final duty rating with GenPro.
Which engine brands are available at this output?
The comparison above includes Baudouin, Perkins, Scania. Some are close alternatives rather than an exact match; use the electrical rating table to compare them.
Electrical output comparison
| Model | Engine brand | Format | Prime | Standby | Voltage |
|---|---|---|---|---|---|
| GPS810BS | Baudouin | Acoustic canopied | 730 kVA | 805 kVA | 400 V |
| GPS810B | Baudouin | Open set | 730 kVA | 805 kVA | 400 V |
| GPS730BS | Baudouin | Acoustic canopied | 658 kVA | 725 kVA | 400 V |
| GPS730B | Baudouin | Open set | 658 kVA | 724 kVA | 400 V |
| GPS720PS | Perkins | Acoustic canopied | 670 kVA | 721 kVA | 400 V |
| GPS720P | Perkins | Open set | 670 kVA | 720 kVA | 400 V |
| GPS810PS | Perkins | Acoustic canopied | 741 kVA | 814 kVA | 400 V |
| GPS810P | Perkins | Open set | 741 kVA | 814 kVA | 400 V |
| GPS820PS | Perkins | Acoustic canopied | 743 kVA | 816 kVA | 400 V |
| GPS820P | Perkins | Open set | 743 kVA | 816 kVA | 400 V |
| GPS710SS | Scania | Acoustic canopied | 647 kVA | 711 kVA | 400 V |
| GPS710S | Scania | Open set | 647 kVA | 711 kVA | 400 V |
| GPS830PS | Perkins | Acoustic canopied | 750 kVA | 825 kVA | 400 V |
| GPS830P | Perkins | Open set | 750 kVA | 825 kVA | 400 V |
| GPS780SS | Scania | Acoustic canopied | 708 kVA | 776 kVA | 400 V |
| GPS780S | Scania | Open set | 708 kVA | 776 kVA | 400 V |