A model-specific render and installation drawing will be supplied with the quotation.
Designed and manufacturedin the United KingdomScania / Open set / 50 Hz
780 kVA class
Scania diesel generator
Open set generator with a DC16078A-02-43 engine and Mecc Alte ECO40-VL4C reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.
Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.
Price and lead time confirmed with your quotation.
Technical specification.
| GenPro model | GPS780S |
|---|---|
| Engine brand / model | Scania DC16078A-02-43 |
| Alternator | Mecc Alte ECO40-VL4C |
| Frequency | 50 Hz |
| Reference voltage | 400 V |
| Reference phase | 3 phase |
| Exact prime rating | 708 kVA / 566 kW |
| Exact standby rating | 776 kVA / 621 kW |
| Aspiration | Turbocharged |
|---|---|
| Governor | ECU |
| No. of Cylinders | 8 |
| Cylinder Arrangement | At Vee |
| Displacement | 16.4L |
| Cooling Type | Liquid Cooled |
| Coolant Capacity | 68L |
| Oil Capacity | 48L |
| Type | Brushless |
| Poles | 4 |
| AVR Model | DER-1/A |
| Voltage Regulation | 1% |
| Insulation Class | H |
| Excitation | Self Excited |
Voltage-specific ratings
Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.
| Voltage | ESP kVA | ESP kW | PRP kVA | PRP kW |
|---|---|---|---|---|
| 380 V | 774 kVA | 619 kW | 706 kVA | 565 kW |
| 400 V | 776 kVA | 621 kW | 708 kVA | 566 kW |
Configuration options.
These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.
| Engine | Alternator | Phase | Voltage | Prime / PRP | Standby / ESP |
|---|---|---|---|---|---|
| DC16078A-02-43 | Mecc Alte ECO40-VL4C | 3 | 400 V | 708 kVA | 776 kVA |
Installation & enclosure
| Reference weight | 3340.8 kg |
|---|---|
| Configuration market | UK/EU |
Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.
Fuel consumption
| 50% Load | 69 litres/hour |
|---|---|
| 75% Load | 103.6 litres/hour |
| 100% Load | 139.5 litres/hour |
| 110% Load | 156.8 litres/hour |
Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.