GENPRO / UK DESIGNED & MANUFACTURED GENERATORS+44 (0)121 517 0315
GENPRO / ACOUSTIC CANOPIEDGPS810PSPerkins · 4006-23TAG2ABuild-specific image supplied with quotation

A model-specific render and installation drawing will be supplied with the quotation.

Perkins engine manufacturer logo
Designed and manufactured in the United KingdomDesigned and manufactured
in the United Kingdom
Perkins / Acoustic canopied / 50 Hz

810 kVA class
Perkins diesel generator

GPS810PS

Acoustic canopied generator with a 4006-23TAG2A engine and Stamford S6L1D-C41 reference alternator. Acoustic canopy and sound requirements to be confirmed for your application.

Prime / PRP741 kVA593 kW
Standby / ESP814 kVA651 kW

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS810PS
Engine brand / modelPerkins 4006-23TAG2A
AlternatorStamford S6L1D-C41
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating741 kVA / 593 kW
Exact standby rating814 kVA / 651 kW
AspirationTurbocharged
GovernorElectronic
No. of Cylinders6
Cylinder ArrangementIn Line
Displacement22.92L
Cooling TypeLiquid Cooled
Coolant Capacity120L
Oil Capacity113L
TypeBrushless
Poles4
AVR ModelMX321
Voltage Regulation0.5%
Insulation ClassH
ExcitationPMG

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
380 V813 kVA650 kW740 kVA592 kW
400 V814 kVA651 kW741 kVA593 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
4006-23TAG2AStamford S6L1D-C413400 V741 kVA814 kVA

Installation & enclosure

Dimensions, weight and fuel tankConfirmed with quotation and build drawing

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load80 litres/hour
75% Load117 litres/hour
100% Load155 litres/hour
110% Load169 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.

Compare your options

Related generators.

Let’s specify your next generator.

Tell us your load, site and application. We’ll help you choose the right configuration.

Talk to GenPro
Call GenProRequest a quote