GENPRO / OPEN SETGPS820PPerkins · 4006-23TAG2ABuild-specific image supplied with quotation

A model-specific render and installation drawing will be supplied with the quotation.

Perkins engine manufacturer logo
Designed and manufactured in the United KingdomDesigned and manufactured
in the United Kingdom
Perkins / Open set / 50 Hz

820 kVA class
Perkins diesel generator

GPS820P

Open set generator with a 4006-23TAG2A engine and Leroy Somer TAL049C reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.

Prime / PRP743 kVA594 kW
Standby / ESP816 kVA653 kW

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS820P
Engine brand / modelPerkins 4006-23TAG2A
AlternatorLeroy Somer TAL049C
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating743 kVA / 594 kW
Exact standby rating816 kVA / 653 kW
AspirationTurbocharged
GovernorElectronic
No. of Cylinders6
Cylinder ArrangementIn Line
Displacement22.92L
Cooling TypeLiquid Cooled
Coolant Capacity120L
Oil Capacity113L
TypeBrushless
Poles4
AVR ModelR150
Voltage Regulation1%
Insulation ClassH
ExcitationSelf Excited

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
400 V816 kVA653 kW743 kVA594 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
4006-23TAG2ALeroy Somer TAL049C3400 V743 kVA816 kVA

Installation & enclosure

Dimensions, weight and fuel tankConfirmed with quotation and build drawing

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load80 litres/hour
75% Load117 litres/hour
100% Load155 litres/hour
110% Load169 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.