GENPRO / UK DESIGNED & MANUFACTURED GENERATORS+44 (0)121 517 0315
Generator power guide

1,750 kVA diesel generators.

Compare UK-designed and UK-manufactured 1,750 kVA diesel generator options and nearby ratings from Baudouin, Cummins, Perkins. Check the exact prime and standby output, engine and enclosure before selecting.

Compare exact outputs

Options around 1,750 kVA.

A rounded GPS model class is not a guaranteed duty rating. The tables below identify the actual documented output for each reference configuration.

High-capacity power projects

Specify 1,750 kVA around your load.

High-capacity installations need a complete engineering review of load behaviour, cooling, exhaust, fuel storage, switching and service access. Confirm the installation drawing and rated operating conditions before procurement.

At a power factor of 0.8, 1,750 kVA corresponds to 1400 kW mathematically. That conversion is not a substitute for the manufacturer’s duty rating or a starting-load assessment.

Discuss your load schedule
Does a 1,750 kVA model deliver 1,750 kVA continuously?

The model class alone does not establish continuous capability. Check prime and standby ratings and the manufacturer’s load-profile conditions. Confirm the intended run hours and average load when requesting a quotation.

Can I get a canopied 1,750 kVA generator?

Compare the canopied entries above, then confirm enclosure dimensions, sound requirements and final duty rating with GenPro.

Which engine brands are available at this output?

The comparison above includes Baudouin, Cummins, Perkins. Some are close alternatives rather than an exact match; use the electrical rating table to compare them.

Electrical output comparison

ModelEngine brandFormatPrimeStandbyVoltage
GPS1900BSBaudouinAcoustic canopied1746 kVA1922 kVA400 V
GPS1900BBaudouinOpen set1746 kVA1922 kVA400 V
GPS1900PSPerkinsAcoustic canopied1729 kVA1897 kVA400 V
GPS1900PPerkinsOpen set1729 kVA1897 kVA400 V
GPS1850PSPerkinsAcoustic canopied1728 kVA1873 kVA400 V
GPS1850PPerkinsOpen set1728 kVA1873 kVA400 V
GPS1800CSCumminsAcoustic canopied1647 kVA1818 kVA400 V
GPS1800CCumminsOpen set1647 kVA1818 kVA400 V
GPS1700BSBaudouinAcoustic canopied1562 kVA1678 kVA400 V
GPS1700BBaudouinOpen set1562 kVA1678 kVA400 V
GPS1650BSBaudouinAcoustic canopied1550 kVA1660 kVA400 V
GPS1650PSPerkinsAcoustic canopied1511 kVA1660 kVA400 V
GPS1650PPerkinsOpen set1511 kVA1660 kVA400 V
GPS1650CSCumminsAcoustic canopied1400 kVA1652 kVA400 V
GPS1650CCumminsOpen set1400 kVA1652 kVA400 V
GPS1650BBaudouinOpen set1500 kVA1650 kVA400 V

Let’s specify your next generator.

Tell us your load, site and application. We’ll help you choose the right configuration.

Talk to GenPro
Call GenProRequest a quote