GENPRO / UK DESIGNED & MANUFACTURED GENERATORS+44 (0)121 517 0315
GENPRO / ACOUSTIC CANOPIEDGPS1650BSBaudouin · 12M33G1650/5Build-specific image supplied with quotation

A model-specific render and installation drawing will be supplied with the quotation.

Baudouin engine manufacturer logo
Designed and manufactured in the United KingdomDesigned and manufactured
in the United Kingdom
Baudouin / Acoustic canopied / 50 Hz

1,650 kVA class
Baudouin diesel generator

GPS1650BS

Acoustic canopied generator with a 12M33G1650/5 engine and Stamford S7L1D-C41 reference alternator. Acoustic canopy and sound requirements to be confirmed for your application.

Prime / PRP1550 kVA1240 kW
Standby / ESP1660 kVA1328 kW

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS1650BS
Engine brand / modelBaudouin 12M33G1650/5
AlternatorStamford S7L1D-C41
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating1550 kVA / 1240 kW
Exact standby rating1660 kVA / 1328 kW
AspirationTurbocharged
GovernorElectronic
No. of Cylinders12
Cylinder ArrangementAt Vee
Displacement39.2L
Cooling TypeLiquid Cooled
Coolant Capacity188L
Oil Capacity160L
TypeBrushless
Poles4
AVR ModelMX341
Voltage Regulation1%
Insulation ClassH
ExcitationPMG

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
380 V1615 kVA1292 kW1505 kVA1204 kW
400 V1660 kVA1328 kW1550 kVA1240 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
12M33G1650/5Stamford S7L1D-C413400 V1550 kVA1660 kVA
12M33G1650/5Leroy Somer LSA50.2L83400 V1500 kVA1650 kVA

Installation & enclosure

Dimensions, weight and fuel tankConfirmed with quotation and build drawing

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load156.1 litres/hour
75% Load234.2 litres/hour
100% Load324 litres/hour
110% Load354.2 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.