1,850 kVA class
Perkins generator
4012-46TAG3A

Representative generator image; final appearance follows the confirmed build specification.
Designed and manufacturedOpen set generator with a 4012-46TAG3A engine and Stamford S7L1D-E41 reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.
Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.
Price and lead time confirmed with your quotation.
| GenPro model | GPS1850P |
|---|---|
| Engine brand / model | Perkins 4012-46TAG3A |
| Alternator | Stamford S7L1D-E41 |
| Frequency | 50 Hz |
| Reference voltage | 400 V |
| Reference phase | 3 phase |
| Exact prime rating | 1728 kVA / 1382 kW |
| Exact standby rating | 1873 kVA / 1498 kW |
| Aspiration | Turbocharged |
|---|---|
| Governor | Electronic |
| No. of Cylinders | 12 |
| Cylinder Arrangement | At Vee |
| Displacement | 45.84L |
| Cooling Type | Liquid Cooled |
| Coolant Capacity | 233L |
| Oil Capacity | 157.5L |
| Type | Brushless |
| Poles | 4 |
| AVR Model | MX341 |
| Voltage Regulation | 1% |
| Insulation Class | H |
| Excitation | PMG |
Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.
| Voltage | ESP kVA | ESP kW | PRP kVA | PRP kW |
|---|---|---|---|---|
| 380 V | 1819 kVA | 1455 kW | 1700 kVA | 1360 kW |
| 400 V | 1873 kVA | 1498 kW | 1728 kVA | 1382 kW |
These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.
| Engine | Alternator | Phase | Voltage | Prime / PRP | Standby / ESP |
|---|---|---|---|---|---|
| 4012-46TAG3A | Stamford S7L1D-E41 | 3 | 400 V | 1728 kVA | 1873 kVA |
| Dimensions (L × W × H) | 4948 × 2164 × 2782 mm |
|---|---|
| Reference weight | 10451.5 kg |
| Configuration market | Export |
Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.
| 50% Load | 188.8 litres/hour |
|---|---|
| 75% Load | 280.5 litres/hour |
| 100% Load | 363.3 litres/hour |
| 110% Load | 401.3 litres/hour |
Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.
4012-46TAG3A