GENPRO / UK DESIGNED & MANUFACTURED GENERATORS+44 (0)121 517 0315
GENPRO / OPEN SETGPS60PPerkins · 1103A-33TG2Build-specific image supplied with quotation

A model-specific render and installation drawing will be supplied with the quotation.

Perkins engine manufacturer logo
Designed and manufactured in the United KingdomDesigned and manufactured
in the United Kingdom
Perkins / Open set / 50 Hz

60 kVA class
Perkins diesel generator

GPS60P

Open set generator with a 1103A-33TG2 engine and Stamford UCi274C1 reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.

Prime / PRP56 kVA45 kW
Standby / ESP60 kVA48 kW

Exact ratings above: 230 V, 1-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS60P
Engine brand / modelPerkins 1103A-33TG2
AlternatorStamford UCi274C1
Frequency50 Hz
Reference voltage230 V
Reference phase1 phase
Exact prime rating56 kVA / 45 kW
Exact standby rating60 kVA / 48 kW
AspirationTurbocharged
GovernorMechanical
No. of Cylinders3
Cylinder ArrangementIn Line
Displacement3.3L
Cooling TypeLiquid Cooled
Coolant Capacity10.2L
Oil Capacity8.3L

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
220 V60 kVA48 kW56 kVA45 kW
230 V60 kVA48 kW56 kVA45 kW
240 V60 kVA48 kW57 kVA46 kW
110 V60 kVA48 kW56 kVA45 kW
115 V60 kVA48 kW56 kVA45 kW
120 V60 kVA48 kW57 kVA46 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
1103A-33TG2Stamford UCi274C11230 V56 kVA60 kVA
1103A-33TG2Leroy Somer TAL044D1230 V58 kVA63 kVA

Installation & enclosure

Dimensions, weight and fuel tankConfirmed with quotation and build drawing

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load7.56 litres/hour
75% Load10.8 litres/hour
100% Load14.6 litres/hour
110% Load15.9 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.

Compare your options

Related generators.

Let’s specify your next generator.

Tell us your load, site and application. We’ll help you choose the right configuration.

Talk to GenPro
Call GenProRequest a quote