A model-specific render and installation drawing will be supplied with the quotation.
Designed and manufacturedin the United KingdomPerkins / Open set / 50 Hz
70 kVA class
Perkins diesel generator
Open set generator with a 1103A-33TG2 engine and Leroy Somer TAL042H reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.
Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.
Price and lead time confirmed with your quotation.
Technical specification.
| GenPro model | GPS70P |
|---|---|
| Engine brand / model | Perkins 1103A-33TG2 |
| Alternator | Leroy Somer TAL042H |
| Frequency | 50 Hz |
| Reference voltage | 400 V |
| Reference phase | 3 phase |
| Exact prime rating | 60 kVA / 48 kW |
| Exact standby rating | 66 kVA / 53 kW |
| Aspiration | Turbocharged |
|---|---|
| Governor | Mechanical |
| No. of Cylinders | 3 |
| Cylinder Arrangement | In Line |
| Displacement | 3.3L |
| Cooling Type | Liquid Cooled |
| Coolant Capacity | 10.2L |
| Oil Capacity | 8.3L |
| Type | Brushless |
| Poles | 4 |
| AVR Model | R120 |
| Voltage Regulation | 1% |
| Insulation Class | H |
| Excitation | Self Excited |
Voltage-specific ratings
Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.
| Voltage | ESP kVA | ESP kW | PRP kVA | PRP kW |
|---|---|---|---|---|
| 400 V | 66 kVA | 53 kW | 60 kVA | 48 kW |
Configuration options.
These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.
| Engine | Alternator | Phase | Voltage | Prime / PRP | Standby / ESP |
|---|---|---|---|---|---|
| 1103A-33TG2 | Leroy Somer TAL042H | 3 | 400 V | 60 kVA | 66 kVA |
| 1104A-44TG1 | Stamford UCI224F1 | 3 | 400 V | 66 kVA | 72 kVA |
| 1104A-44TG1 | Stamford UCI224G1 | 3 | 400 V | 66 kVA | 72 kVA |
| 1103A-33TG2 | Stamford S1L2-Y1 | 3 | 400 V | 61 kVA | 66 kVA |
| 1104A-44TG1 | Leroy Somer TAL044A | 3 | 400 V | 66 kVA | 72 kVA |
| 1103A-33TG2 | Leroy Somer TAL044A | 3 | 400 V | 61 kVA | 67 kVA |
| 1103A-33TG2 | KWise C224G50 | 3 | 400 V | 60 kVA | 66 kVA |
Installation & enclosure
| Dimensions (L × W × H) | 1700 × 702 × 1388 mm |
|---|---|
| Reference weight | 811.9 kg |
| Reference fuel tank | 125 litres |
| Configuration market | Export |
Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.
Fuel consumption
| 50% Load | 7.56 litres/hour |
|---|---|
| 75% Load | 10.8 litres/hour |
| 100% Load | 14.6 litres/hour |
| 110% Load | 15.9 litres/hour |
Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.