GENPRO / UK DESIGNED & MANUFACTURED GENERATORS+44 (0)121 517 0315
GENPRO / OPEN SETGPS50PPerkins · 1103A-33TG1Build-specific image supplied with quotation

A model-specific render and installation drawing will be supplied with the quotation.

Perkins engine manufacturer logo
Designed and manufactured in the United KingdomDesigned and manufactured
in the United Kingdom
Perkins / Open set / 50 Hz

50 kVA class
Perkins diesel generator

GPS50P

Open set generator with a 1103A-33TG1 engine and Leroy Somer TAL042F reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.

Prime / PRP45 kVA36 kW
Standby / ESP50 kVA40 kW

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS50P
Engine brand / modelPerkins 1103A-33TG1
AlternatorLeroy Somer TAL042F
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating45 kVA / 36 kW
Exact standby rating50 kVA / 40 kW
AspirationTurbocharged
GovernorMechanical
No. of Cylinders3
Cylinder ArrangementIn Line
Displacement3.3L
Cooling TypeLiquid Cooled
Coolant Capacity11.8L
Oil Capacity8.3L
TypeBrushless
Poles4
AVR ModelR120
Voltage Regulation1%
Insulation ClassH
ExcitationSelf Excited

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
400 V50 kVA40 kW45 kVA36 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
1103A-33TG1Leroy Somer TAL042F3400 V45 kVA50 kVA
1103A-33TG1KWise C224G403400 V46 kVA51 kVA
1103A-33TG1Stamford S1L2-N13400 V45 kVA50 kVA
1103A-33TG1Stamford UCI224F13400 V46 kVA51 kVA
1103A-33TG1Stamford UCI224G11230 V42.2 kVA46.6 kVA
1103A-33TG1Leroy Somer TAL044B1230 V44.2 kVA48 kVA

Installation & enclosure

Dimensions (L × W × H)1700 × 702 × 1388 mm
Reference weight805.9 kg
Reference fuel tank125 litres
Configuration marketExport

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load5.58 litres/hour
75% Load7.98 litres/hour
100% Load10.52 litres/hour
110% Load11.77 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.

Compare your options

Related generators.

Let’s specify your next generator.

Tell us your load, site and application. We’ll help you choose the right configuration.

Talk to GenPro
Call GenProRequest a quote