GENPRO / UK DESIGNED & MANUFACTURED GENERATORS+44 (0)121 517 0315
GENPRO / OPEN SETGPS550BBaudouin · 6M21G8D0/SBuild-specific image supplied with quotation

A model-specific render and installation drawing will be supplied with the quotation.

Baudouin engine manufacturer logo
Designed and manufactured in the United KingdomDesigned and manufactured
in the United Kingdom
Baudouin / Open set / 50 Hz

550 kVA class
Baudouin diesel generator

GPS550B

Open set generator with a 6M21G8D0/S engine and Leroy Somer TAL0473C reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.

Prime / PRP500 kVA400 kW
Standby / ESP550 kVA440 kW

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS550B
Engine brand / modelBaudouin 6M21G8D0/S
AlternatorLeroy Somer TAL0473C
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating500 kVA / 400 kW
Exact standby rating550 kVA / 440 kW
AspirationTurbocharged
GovernorECU
No. of Cylinders6
Cylinder ArrangementIn Line
Displacement12.54L
Cooling TypeLiquid Cooled
Coolant Capacity62L
Oil Capacity40L
TypeBrushless
Poles4
AVR ModelR150
Voltage Regulation1.0% Regulation%
Insulation ClassH
ExcitationBrushless

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
400 V550 kVA440 kW500 kVA400 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
6M21G8D0/SLeroy Somer TAL0473C3400 V500 kVA550 kVA

Installation & enclosure

Reference weight2970.85 kg
Reference fuel tank590 litres
Configuration marketUK/EU

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load51 litres/hour
75% Load75.3 litres/hour
100% Load109.5 litres/hour
110% Load123.1 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.

Compare your options

Related generators.

Let’s specify your next generator.

Tell us your load, site and application. We’ll help you choose the right configuration.

Talk to GenPro