
Representative generator image; final appearance follows the confirmed build specification.
Designed and manufacturedin the United KingdomBaudouin / Acoustic canopied / 50 Hz
560 kVA class
Baudouin diesel generator
Acoustic canopied generator with a 6M21G550/5 engine and Stamford HCI544D1 reference alternator. Acoustic canopy and sound requirements to be confirmed for your application.
Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.
Price and lead time confirmed with your quotation.
Technical specification.
| GenPro model | GPS560BS |
|---|---|
| Engine brand / model | Baudouin 6M21G550/5 |
| Alternator | Stamford HCI544D1 |
| Frequency | 50 Hz |
| Reference voltage | 400 V |
| Reference phase | 3 phase |
| Exact prime rating | 514 kVA / 411 kW |
| Exact standby rating | 559 kVA / 447 kW |
| Aspiration | Turbocharged |
|---|---|
| Governor | ECU |
| No. of Cylinders | 6 |
| Cylinder Arrangement | In Line |
| Displacement | 12.54L |
| Cooling Type | Liquid Cooled |
| Coolant Capacity | 62L |
| Oil Capacity | 40L |
| Type | Brushless |
| Poles | 4 |
| AVR Model | AS440 |
| Voltage Regulation | 1% |
| Insulation Class | H |
| Excitation | Self Excited |
Voltage-specific ratings
Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.
| Voltage | ESP kVA | ESP kW | PRP kVA | PRP kW |
|---|---|---|---|---|
| 190 V | 550 kVA | 440 kW | 500 kVA | 400 kW |
| 200 V | 559 kVA | 447 kW | 514 kVA | 411 kW |
| 208 V | 550 kVA | 440 kW | 500 kVA | 400 kW |
| 220 V | 530 kVA | 424 kW | 500 kVA | 400 kW |
| 220 V | 550 kVA | 440 kW | 500 kVA | 400 kW |
| 230 V | 559 kVA | 447 kW | 514 kVA | 411 kW |
| 240 V | 550 kVA | 440 kW | 500 kVA | 400 kW |
| 254 V | 530 kVA | 424 kW | 500 kVA | 400 kW |
| 380 V | 550 kVA | 440 kW | 500 kVA | 400 kW |
| 400 V | 559 kVA | 447 kW | 514 kVA | 411 kW |
| 415 V | 550 kVA | 440 kW | 500 kVA | 400 kW |
| 440 V | 530 kVA | 424 kW | 500 kVA | 400 kW |
Configuration options.
These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.
| Engine | Alternator | Phase | Voltage | Prime / PRP | Standby / ESP |
|---|---|---|---|---|---|
| 6M21G550/5 | Stamford HCI544D1 | 3 | 400 V | 514 kVA | 559 kVA |
| 6M21G8D0/S | Stamford S5L1D-D41 | 3 | 400 V | 514 kVA | 559 kVA |
| 6M21G8D0/S | Stamford HCI544D1 | 3 | 400 V | 514 kVA | 559 kVA |
Installation & enclosure
| Dimensions (L × W × H) | 3958 × 1504 × 2384 mm |
|---|---|
| Reference weight | 4041.85 kg |
| Reference fuel tank | 500 litres |
| Configuration market | UK/EU |
| Manufacturer noise reference at 7 m | 76 dB(A) |
Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.
Fuel consumption
| 50% Load | 51 litres/hour |
|---|---|
| 75% Load | 75.3 litres/hour |
| 100% Load | 109.5 litres/hour |
| 110% Load | 123.1 litres/hour |
Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.


