GenPro-branded enclosure reference; final appearance follows the confirmed build specification.
Designed and manufacturedin the United KingdomPerkins / Acoustic canopied / 50 Hz
50 kVA class
Perkins diesel generator
Acoustic canopied generator with a 1103A-33TG1 engine and Stamford S1L2-N1 reference alternator. Acoustic canopy and sound requirements to be confirmed for your application.
Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.
Price and lead time confirmed with your quotation.
Technical specification.
| GenPro model | GPS50PS |
|---|---|
| Engine brand / model | Perkins 1103A-33TG1 |
| Alternator | Stamford S1L2-N1 |
| Frequency | 50 Hz |
| Reference voltage | 400 V |
| Reference phase | 3 phase |
| Exact prime rating | 45 kVA / 36 kW |
| Exact standby rating | 50 kVA / 40 kW |
| Aspiration | Turbocharged |
|---|---|
| Governor | Mechanical |
| No. of Cylinders | 3 |
| Cylinder Arrangement | In Line |
| Displacement | 3.3L |
| Cooling Type | Liquid Cooled |
| Coolant Capacity | 11.8L |
| Oil Capacity | 8.3L |
| Type | Brushless |
| Poles | 4 |
| AVR Model | AS540 |
| Voltage Regulation | 1% |
| Insulation Class | H |
| Excitation | Self Excited |
Voltage-specific ratings
Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.
| Voltage | ESP kVA | ESP kW | PRP kVA | PRP kW |
|---|---|---|---|---|
| 200 V | 50 kVA | 40 kW | 45 kVA | 36 kW |
| 208 V | 50 kVA | 40 kW | 45 kVA | 36 kW |
| 230 V | 50 kVA | 40 kW | 45 kVA | 36 kW |
| 240 V | 50 kVA | 40 kW | 45 kVA | 36 kW |
| 400 V | 50 kVA | 40 kW | 45 kVA | 36 kW |
| 415 V | 50 kVA | 40 kW | 45 kVA | 36 kW |
Configuration options.
These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.
| Engine | Alternator | Phase | Voltage | Prime / PRP | Standby / ESP |
|---|---|---|---|---|---|
| 1103A-33TG1 | Stamford S1L2-N1 | 3 | 400 V | 45 kVA | 50 kVA |
| 1103A-33TG1 | Stamford UCI224F1 | 3 | 400 V | 46 kVA | 51 kVA |
| 1103A-33TG1 | Leroy Somer TAL042F | 3 | 400 V | 45 kVA | 50 kVA |
| 1103A-33TG1 | KWise C224G40 | 3 | 400 V | 46 kVA | 51 kVA |
| 1103A-33TG1 | Stamford UCI224G1 | 1 | 230 V | 42.2 kVA | 46.6 kVA |
| 1103A-33TG1 | Leroy Somer TAL044B | 1 | 230 V | 44.2 kVA | 48 kVA |
Installation & enclosure
| Dimensions (L × W × H) | 2240 × 1038 × 1378 mm |
|---|---|
| Reference weight | 1159.9 kg |
| Reference fuel tank | 80 litres |
| Configuration market | UK/EU |
| Manufacturer noise reference at 7 m | 76 dB(A) |
Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.
Fuel consumption
| 50% Load | 5.58 litres/hour |
|---|---|
| 75% Load | 7.98 litres/hour |
| 100% Load | 10.52 litres/hour |
| 110% Load | 11.77 litres/hour |
Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.