GENPRO / UK DESIGNED & MANUFACTURED GENERATORS+44 (0)121 517 0315
GENPRO / OPEN SETGPS900BBaudouin · 12M26G900/5Build-specific image supplied with quotation

A model-specific render and installation drawing will be supplied with the quotation.

Baudouin engine manufacturer logo
Designed and manufactured in the United KingdomDesigned and manufactured
in the United Kingdom
Baudouin / Open set / 50 Hz

900 kVA class
Baudouin diesel generator

GPS900B

Open set generator with a 12M26G900/5 engine and Leroy Somer TAL049C reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.

Prime / PRP820 kVA656 kW
Standby / ESP904 kVA723 kW

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS900B
Engine brand / modelBaudouin 12M26G900/5
AlternatorLeroy Somer TAL049C
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating820 kVA / 656 kW
Exact standby rating904 kVA / 723 kW
AspirationTurbocharged
GovernorElectronic
No. of Cylinders12
Cylinder ArrangementAt Vee
Displacement31.8L
Cooling TypeLiquid Cooled
Coolant Capacity148L
Oil Capacity114L
TypeBrushless
Poles4
AVR ModelR150
Voltage Regulation1%
Insulation ClassH
ExcitationSelf Excited

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
400 V904 kVA723 kW820 kVA656 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
12M26G900/5Leroy Somer TAL049C3400 V820 kVA904 kVA

Installation & enclosure

Reference weight5943.5 kg
Configuration marketExport

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load90.8 litres/hour
75% Load133.1 litres/hour
100% Load173.7 litres/hour
110% Load190.8 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.