GENPRO / UK DESIGNED & MANUFACTURED GENERATORS+44 (0)121 517 0315
GENPRO / OPEN SETGPS880CCummins · QSK23G3Build-specific image supplied with quotation

A model-specific render and installation drawing will be supplied with the quotation.

Cummins engine manufacturer logo
Designed and manufactured in the United KingdomDesigned and manufactured
in the United Kingdom
Cummins / Open set / 50 Hz

880 kVA class
Cummins diesel generator

GPS880C

Open set generator with a QSK23G3 engine and Stamford S6L1D-D41 reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.

Prime / PRP812 kVA650 kW
Standby / ESP880 kVA704 kW

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS880C
Engine brand / modelCummins QSK23G3
AlternatorStamford S6L1D-D41
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating812 kVA / 650 kW
Exact standby rating880 kVA / 704 kW
AspirationTurbocharged
GovernorElectronic
No. of Cylinders6
Cylinder ArrangementIn Line
Displacement23.15L
Cooling TypeLiquid Cooled
Coolant Capacity109.5L
Oil Capacity103L
TypeBrushless
Poles4
AVR ModelMX321
Voltage Regulation0.5%
Insulation ClassH
ExcitationPMG

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
380 V880 kVA704 kW812 kVA650 kW
400 V880 kVA704 kW812 kVA650 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
QSK23G3Stamford S6L1D-D413400 V812 kVA880 kVA

Installation & enclosure

Dimensions, weight and fuel tankConfirmed with quotation and build drawing

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load85 litres/hour
75% Load121 litres/hour
100% Load161 litres/hour
110% Load178 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.

Compare your options

Related generators.

Let’s specify your next generator.

Tell us your load, site and application. We’ll help you choose the right configuration.

Talk to GenPro
Call GenProRequest a quote