GENPRO / UK DESIGNED & MANUFACTURED GENERATORS+44 (0)121 517 0315
Scania acoustic canopied generator — representative configuration image

GenPro-branded enclosure reference; final appearance follows the confirmed build specification.

Scania engine manufacturer logo
Designed and manufactured in the United KingdomDesigned and manufactured
in the United Kingdom
Scania / Acoustic canopied / 50 Hz

570 kVA class
Scania diesel generator

GPS570SS

Acoustic canopied generator with a DC16093A-02-51 engine and Stamford HCI544E1 reference alternator. Acoustic canopy and sound requirements to be confirmed for your application.

Prime / PRP520 kVA416 kW
Standby / ESP571 kVA457 kW

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS570SS
Engine brand / modelScania DC16093A-02-51
AlternatorStamford HCI544E1
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating520 kVA / 416 kW
Exact standby rating571 kVA / 457 kW
AspirationTurbocharged
GovernorECU
No. of Cylinders8
Cylinder ArrangementAt Vee
Displacement16.4L
Cooling TypeLiquid Cooled
Coolant Capacity68L
Oil Capacity48L
TypeBrushless
Poles4
AVR ModelAS440
Voltage Regulation1%
Insulation ClassH
ExcitationSelf Excited

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
190 V569 kVA455 kW519 kVA415 kW
200 V571 kVA457 kW520 kVA416 kW
208 V572 kVA458 kW520 kVA416 kW
220 V573 kVA458 kW521 kVA417 kW
220 V569 kVA455 kW518 kVA414 kW
230 V571 kVA457 kW520 kVA416 kW
240 V572 kVA458 kW520 kVA416 kW
254 V573 kVA458 kW521 kVA417 kW
380 V569 kVA455 kW518 kVA414 kW
400 V571 kVA457 kW520 kVA416 kW
415 V572 kVA458 kW520 kVA416 kW
440 V573 kVA458 kW521 kVA417 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
DC16093A-02-51Stamford HCI544E13400 V520 kVA571 kVA
DC16093A-02-51Stamford S5L1D-D413400 V516 kVA568 kVA

Installation & enclosure

Dimensions (L × W × H)4908 × 2164 × 2658 mm
Reference weight5666.8 kg
Reference fuel tank1120 litres
Configuration marketUK/EU
Manufacturer noise reference at 7 m76 dB(A)

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load52.3 litres/hour
75% Load75.6 litres/hour
100% Load100.3 litres/hour
110% Load111.5 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.

Compare your options

Related generators.

Let’s specify your next generator.

Tell us your load, site and application. We’ll help you choose the right configuration.

Talk to GenPro
Call GenProRequest a quote