GENPRO / UK DESIGNED & MANUFACTURED GENERATORS+44 (0)121 517 0315
GENPRO / OPEN SETGPS510BBaudouin · 6M21G500/5Build-specific image supplied with quotation

A model-specific render and installation drawing will be supplied with the quotation.

Baudouin engine manufacturer logo
Designed and manufactured in the United KingdomDesigned and manufactured
in the United Kingdom
Baudouin / Open set / 50 Hz

510 kVA class
Baudouin diesel generator

GPS510B

Open set generator with a 6M21G500/5 engine and KWise C354G400 reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.

Prime / PRP460 kVA368 kW
Standby / ESP509 kVA407 kW

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS510B
Engine brand / modelBaudouin 6M21G500/5
AlternatorKWise C354G400
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating460 kVA / 368 kW
Exact standby rating509 kVA / 407 kW
AspirationTurbocharged
GovernorECU
No. of Cylinders6
Cylinder ArrangementIn Line
Displacement12.54L
Cooling TypeLiquid Cooled
Coolant Capacity47L
Oil Capacity40L
TypeBrushless
Poles4
AVR ModelKR440
Voltage Regulation1%
Insulation ClassH
ExcitationPMG

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
200 V509 kVA407 kW460 kVA368 kW
230 V509 kVA407 kW460 kVA368 kW
400 V509 kVA407 kW460 kVA368 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
6M21G500/5KWise C354G4003400 V460 kVA509 kVA

Installation & enclosure

Dimensions, weight and fuel tankConfirmed with quotation and build drawing

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load46.6 litres/hour
75% Load69.6 litres/hour
100% Load95.9 litres/hour
110% Load110.1 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.

Compare your options

Related generators.

Let’s specify your next generator.

Tell us your load, site and application. We’ll help you choose the right configuration.

Talk to GenPro
Call GenProRequest a quote