GENPRO / UK DESIGNED & MANUFACTURED GENERATORS+44 (0)121 517 0315
GENPRO / OPEN SETGPS500BBaudouin · 6M21G500/5Build-specific image supplied with quotation

A model-specific render and installation drawing will be supplied with the quotation.

Baudouin engine manufacturer logo
Designed and manufactured in the United KingdomDesigned and manufactured
in the United Kingdom
Baudouin / Open set / 50 Hz

500 kVA class
Baudouin diesel generator

GPS500B

Open set generator with a 6M21G500/5 engine and Stamford S4L1D-G41 reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.

Prime / PRP450 kVA360 kW
Standby / ESP495 kVA396 kW

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS500B
Engine brand / modelBaudouin 6M21G500/5
AlternatorStamford S4L1D-G41
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating450 kVA / 360 kW
Exact standby rating495 kVA / 396 kW
AspirationTurbocharged
GovernorECU
No. of Cylinders6
Cylinder ArrangementIn Line
Displacement12.54L
Cooling TypeLiquid Cooled
Coolant Capacity47L
Oil Capacity40L
TypeBrushless
Poles4
AVR ModelAS440
Voltage Regulation1%
Insulation ClassH
ExcitationSelf Excited

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
190 V475 kVA380 kW430 kVA344 kW
200 V495 kVA396 kW450 kVA360 kW
208 V496 kVA397 kW450 kVA360 kW
220 V475 kVA380 kW430 kVA344 kW
220 V475 kVA380 kW430 kVA344 kW
230 V495 kVA396 kW450 kVA360 kW
240 V496 kVA397 kW450 kVA360 kW
254 V475 kVA380 kW430 kVA344 kW
380 V475 kVA380 kW430 kVA344 kW
400 V495 kVA396 kW450 kVA360 kW
415 V496 kVA397 kW450 kVA360 kW
440 V475 kVA380 kW430 kVA344 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
6M21G500/5Stamford S4L1D-G413400 V450 kVA495 kVA
6M21G500/5Leroy Somer TAL0473B3400 V455 kVA500 kVA

Installation & enclosure

Reference weight2837 kg
Reference fuel tank730 litres
Configuration marketExport

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load46.6 litres/hour
75% Load69.6 litres/hour
100% Load95.9 litres/hour
110% Load110.1 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.

Compare your options

Related generators.

Let’s specify your next generator.

Tell us your load, site and application. We’ll help you choose the right configuration.

Talk to GenPro