GENPRO / UK DESIGNED & MANUFACTURED GENERATORS+44 (0)121 517 0315
GENPRO / OPEN SETGPS2750BBaudouin · 12M55G2750/5Build-specific image supplied with quotation

A model-specific render and installation drawing will be supplied with the quotation.

Baudouin engine manufacturer logo
Designed and manufactured in the United KingdomDesigned and manufactured
in the United Kingdom
Baudouin / Open set / 50 Hz

2,750 kVA class
Baudouin diesel generator

GPS2750B

Open set generator with a 12M55G2750/5 engine and Stamford S7L1D-J41 reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.

Prime / PRP2500 kVA2000 kW
Standby / ESP2750 kVA2200 kW

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS2750B
Engine brand / modelBaudouin 12M55G2750/5
AlternatorStamford S7L1D-J41
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating2500 kVA / 2000 kW
Exact standby rating2750 kVA / 2200 kW
AspirationTurbocharged
GovernorECU
No. of Cylinders12
Cylinder ArrangementAt Vee
Displacement65.65L
Cooling TypeLiquid Cooled
Coolant Capacity526L
Oil Capacity460L
TypeBrushless
Poles4
AVR ModelMX341
Voltage Regulation1%
Insulation ClassH
ExcitationPMG

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
380 V2600 kVA2080 kW2425 kVA1940 kW
400 V2750 kVA2200 kW2500 kVA2000 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
12M55G2750/5Stamford S7L1D-J413400 V2500 kVA2750 kVA

Installation & enclosure

Reference weight18315.5 kg
Configuration marketExport

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load263.3 litres/hour
75% Load381.3 litres/hour
100% Load513.6 litres/hour
110% Load577.2 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.

Compare your options

Related generators.

Let’s specify your next generator.

Tell us your load, site and application. We’ll help you choose the right configuration.

Talk to GenPro
Call GenProRequest a quote