2,550 kVA class
Baudouin generator
20M33G2500/5
A model-specific render and installation drawing will be supplied with the quotation.
Designed and manufacturedOpen set generator with a 20M33G2500/5 engine and Stamford S7L1D-J41 reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.
Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.
Price and lead time confirmed with your quotation.
| GenPro model | GPS2550B |
|---|---|
| Engine brand / model | Baudouin 20M33G2500/5 |
| Alternator | Stamford S7L1D-J41 |
| Frequency | 50 Hz |
| Reference voltage | 400 V |
| Reference phase | 3 phase |
| Exact prime rating | 2317 kVA / 1854 kW |
| Exact standby rating | 2553 kVA / 2042 kW |
| Aspiration | Turbocharged |
|---|---|
| Governor | ECU |
| No. of Cylinders | 20 |
| Cylinder Arrangement | At Vee |
| Displacement | 65.4L |
| Cooling Type | Liquid Cooled |
| Coolant Capacity | 397L |
| Oil Capacity | 235L |
| Type | Brushless |
| Poles | 4 |
| AVR Model | MX341 |
| Voltage Regulation | 1% |
| Insulation Class | H |
| Excitation | PMG |
Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.
| Voltage | ESP kVA | ESP kW | PRP kVA | PRP kW |
|---|---|---|---|---|
| 380 V | 2553 kVA | 2042 kW | 2315 kVA | 1852 kW |
| 400 V | 2553 kVA | 2042 kW | 2317 kVA | 1854 kW |
These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.
| Engine | Alternator | Phase | Voltage | Prime / PRP | Standby / ESP |
|---|---|---|---|---|---|
| 20M33G2500/5 | Stamford S7L1D-J41 | 3 | 400 V | 2317 kVA | 2553 kVA |
| Dimensions, weight and fuel tank | Confirmed with quotation and build drawing |
|---|
Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.
| 50% Load | 240.5 litres/hour |
|---|---|
| 75% Load | 360.7 litres/hour |
| 100% Load | 466.4 litres/hour |
| 110% Load | 538.5 litres/hour |
Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.