GENPRO / UK DESIGNED & MANUFACTURED GENERATORS+44 (0)121 517 0315
GENPRO / OPEN SETGPS2250PPerkins · 4016-61TRG2Build-specific image supplied with quotation

A model-specific render and installation drawing will be supplied with the quotation.

Perkins engine manufacturer logo
Designed and manufactured in the United KingdomDesigned and manufactured
in the United Kingdom
Perkins / Open set / 50 Hz

2,250 kVA class
Perkins diesel generator

GPS2250P

Open set generator with a 4016-61TRG2 engine and Stamford S7L1D-G41 reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.

Prime / PRP2021 kVA1617 kW
Standby / ESP2250 kVA1800 kW

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS2250P
Engine brand / modelPerkins 4016-61TRG2
AlternatorStamford S7L1D-G41
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating2021 kVA / 1617 kW
Exact standby rating2250 kVA / 1800 kW
AspirationTurbocharged
GovernorElectronic
No. of Cylinders16
Cylinder ArrangementAt Vee
Displacement61.123L
Cooling TypeLiquid Cooled
Coolant Capacity300L
Oil Capacity213L
TypeBrushless
Poles4
AVR ModelMX341
Voltage Regulation1%
Insulation ClassH
ExcitationPMG

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
380 V2165 kVA1732 kW2020 kVA1616 kW
400 V2250 kVA1800 kW2021 kVA1617 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
4016-61TRG2Stamford S7L1D-G413400 V2021 kVA2250 kVA
4016-61TRG2Stamford S7L1D-G413400 V2021 kVA2250 kVA

Installation & enclosure

Dimensions, weight and fuel tankConfirmed with quotation and build drawing

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load208 litres/hour
75% Load306 litres/hour
100% Load405 litres/hour
110% Load463 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.

Compare your options

Related generators.

Let’s specify your next generator.

Tell us your load, site and application. We’ll help you choose the right configuration.

Talk to GenPro
Call GenProRequest a quote