GENPRO / UK DESIGNED & MANUFACTURED GENERATORS+44 (0)121 517 0315
GENPRO / OPEN SETGPS2200PPerkins · 4016-61TRG2Build-specific image supplied with quotation

A model-specific render and installation drawing will be supplied with the quotation.

Perkins engine manufacturer logo
Designed and manufactured in the United KingdomDesigned and manufactured
in the United Kingdom
Perkins / Open set / 50 Hz

2,200 kVA class
Perkins diesel generator

GPS2200P

Open set generator with a 4016-61TRG2 engine and Leroy Somer LSA52.3S6 reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.

Prime / PRP2000 kVA1600 kW
Standby / ESP2200 kVA1760 kW

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS2200P
Engine brand / modelPerkins 4016-61TRG2
AlternatorLeroy Somer LSA52.3S6
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating2000 kVA / 1600 kW
Exact standby rating2200 kVA / 1760 kW
AspirationTurbocharged
GovernorElectronic
No. of Cylinders16
Cylinder ArrangementAt Vee
Displacement61.123L
Cooling TypeLiquid Cooled
Coolant Capacity300L
Oil Capacity213L
TypeBrushless
Poles4
AVR ModelD550
Voltage Regulation0.5%
Insulation ClassH
ExcitationAuxiliary Wound

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
400 V2200 kVA1760 kW2000 kVA1600 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
4016-61TRG2Leroy Somer LSA52.3S63400 V2000 kVA2200 kVA

Installation & enclosure

Dimensions, weight and fuel tankConfirmed with quotation and build drawing

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load208 litres/hour
75% Load306 litres/hour
100% Load405 litres/hour
110% Load463 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.