GENPRO / UK DESIGNED & MANUFACTURED GENERATORS+44 (0)121 517 0315
GENPRO / ACOUSTIC CANOPIEDGPS1000PSPerkins · 4008TAG1ABuild-specific image supplied with quotation

A model-specific render and installation drawing will be supplied with the quotation.

Perkins engine manufacturer logo
Designed and manufactured in the United KingdomDesigned and manufactured
in the United Kingdom
Perkins / Acoustic canopied / 50 Hz

1,000 kVA class
Perkins diesel generator

GPS1000PS

Acoustic canopied generator with a 4008TAG1A engine and Stamford S6L1D-D41 reference alternator. Acoustic canopy and sound requirements to be confirmed for your application.

Prime / PRP911 kVA729 kW
Standby / ESP1000 kVA800 kW

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS1000PS
Engine brand / modelPerkins 4008TAG1A
AlternatorStamford S6L1D-D41
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating911 kVA / 729 kW
Exact standby rating1000 kVA / 800 kW
AspirationTurbocharged
GovernorElectronic
No. of Cylinders8
Cylinder ArrangementIn Line
Displacement30.561L
Cooling TypeLiquid Cooled
Coolant Capacity149L
Oil Capacity153L
TypeBrushless
Poles4
AVR ModelMX321
Voltage Regulation0.5%
Insulation ClassH
ExcitationPMG

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
380 V999 kVA799 kW910 kVA728 kW
400 V1000 kVA800 kW911 kVA729 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
4008TAG1AStamford S6L1D-D413400 V911 kVA1000 kVA
4008TAG1ALeroy Somer TAL049D3400 V910 kVA1004 kVA

Installation & enclosure

Dimensions, weight and fuel tankConfirmed with quotation and build drawing

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load98 litres/hour
75% Load143 litres/hour
100% Load195 litres/hour
110% Load218 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.

Compare your options

Related generators.

Let’s specify your next generator.

Tell us your load, site and application. We’ll help you choose the right configuration.

Talk to GenPro