GenPro-branded enclosure reference; final appearance follows the confirmed build specification.
Designed and manufacturedin the United KingdomPerkins / Acoustic canopied / 50 Hz
840 kVA class
Perkins diesel generator
Acoustic canopied generator with a 2806A-E18TTAG5 engine and Stamford S6L1D-C41 reference alternator. Acoustic canopy and sound requirements to be confirmed for your application.
Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.
Price and lead time confirmed with your quotation.
Technical specification.
| GenPro model | GPS840PS |
|---|---|
| Engine brand / model | Perkins 2806A-E18TTAG5 |
| Alternator | Stamford S6L1D-C41 |
| Frequency | 50 Hz |
| Reference voltage | 400 V |
| Reference phase | 3 phase |
| Exact prime rating | 765 kVA / 612 kW |
| Exact standby rating | 843 kVA / 674 kW |
| Aspiration | Turbocharged |
|---|---|
| Governor | Electronic |
| No. of Cylinders | 6 |
| Cylinder Arrangement | In Line |
| Displacement | 18.1L |
| Cooling Type | Liquid Cooled |
| Coolant Capacity | 110.0L |
| Oil Capacity | 68.0L |
| Type | Brushless |
| Poles | 4 |
| AVR Model | MX321 |
| Voltage Regulation | 0.5% |
| Insulation Class | H |
| Excitation | PMG |
Voltage-specific ratings
Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.
| Voltage | ESP kVA | ESP kW | PRP kVA | PRP kW |
|---|---|---|---|---|
| 380 V | 842 kVA | 674 kW | 764 kVA | 611 kW |
| 400 V | 843 kVA | 674 kW | 765 kVA | 612 kW |
Configuration options.
These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.
| Engine | Alternator | Phase | Voltage | Prime / PRP | Standby / ESP |
|---|---|---|---|---|---|
| 2806A-E18TTAG5 | Stamford S6L1D-C41 | 3 | 400 V | 765 kVA | 843 kVA |
Installation & enclosure
| Dimensions (L × W × H) | 4908 × 2164 × 2658 mm |
|---|---|
| Reference weight | 7092.85 kg |
| Reference fuel tank | 1120 litres |
| Configuration market | UK/EU |
| Manufacturer noise reference at 7 m | 76 dB(A) |
Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.
Fuel consumption
| 50% Load | 81 litres/hour |
|---|---|
| 75% Load | 118 litres/hour |
| 100% Load | 162 litres/hour |
| 110% Load | 179 litres/hour |
Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.