GENPRO / UK DESIGNED & MANUFACTURED GENERATORS+44 (0)121 517 0315
GENPRO / OPEN SETGPS770PPerkins · 2806A-E18TAG4Build-specific image supplied with quotation

A model-specific render and installation drawing will be supplied with the quotation.

Perkins engine manufacturer logo
Designed and manufactured in the United KingdomDesigned and manufactured
in the United Kingdom
Perkins / Open set / 50 Hz

770 kVA class
Perkins diesel generator

GPS770P

Open set generator with a 2806A-E18TAG4 engine and Stamford S5L1D-G41 reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.

Prime / PRP700 kVA560 kW
Standby / ESP770 kVA616 kW

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS770P
Engine brand / modelPerkins 2806A-E18TAG4
AlternatorStamford S5L1D-G41
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating700 kVA / 560 kW
Exact standby rating770 kVA / 616 kW
AspirationTurbocharged
GovernorElectronic
No. of Cylinders6
Cylinder ArrangementIn Line
Displacement18.1L
Cooling TypeLiquid Cooled
Coolant Capacity110.0L
Oil Capacity68.0L
TypeBrushless
Poles4
AVR ModelAS440
Voltage Regulation1.0% Regulation%
Insulation ClassH
ExcitationBrushless

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
380 V750 kVA600 kW680 kVA544 kW
400 V770 kVA616 kW700 kVA560 kW
415 V770 kVA616 kW700 kVA560 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
2806A-E18TAG4Stamford S5L1D-G413400 V700 kVA770 kVA
2806A-E18TAG4Stamford S6L1D-C413400 V702 kVA774 kVA

Installation & enclosure

Dimensions, weight and fuel tankConfirmed with quotation and build drawing

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load76 litres/hour
75% Load108 litres/hour
100% Load145 litres/hour
110% Load160 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.

Compare your options