GENPRO / UK DESIGNED & MANUFACTURED GENERATORS+44 (0)121 517 0315
Perkins acoustic canopied generator — representative configuration image

GenPro-branded enclosure reference; final appearance follows the confirmed build specification.

Perkins engine manufacturer logo
Designed and manufactured in the United KingdomDesigned and manufactured
in the United Kingdom
Perkins / Acoustic canopied / 50 Hz

660 kVA class
Perkins diesel generator

GPS660PS

Acoustic canopied generator with a 2806A-E18TAG1A engine and Leroy Somer TAL0473E reference alternator. Acoustic canopy and sound requirements to be confirmed for your application.

Prime / PRP600 kVA480 kW
Standby / ESP660 kVA528 kW

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS660PS
Engine brand / modelPerkins 2806A-E18TAG1A
AlternatorLeroy Somer TAL0473E
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating600 kVA / 480 kW
Exact standby rating660 kVA / 528 kW
AspirationTurbocharged
GovernorElectronic
No. of Cylinders6
Cylinder ArrangementIn Line
Displacement18.1L
Cooling TypeLiquid Cooled
Coolant Capacity61.0L
Oil Capacity62.0L
TypeBrushless
Poles4
AVR ModelR150
Voltage Regulation1.0% Regulation%
Insulation ClassH
ExcitationBrushless

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
400 V660 kVA528 kW600 kVA480 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
2806A-E18TAG1ALeroy Somer TAL0473E3400 V600 kVA660 kVA

Installation & enclosure

Dimensions (L × W × H)4908 × 2164 × 2658 mm
Reference weight6226.9 kg
Reference fuel tank1120 litres
Configuration marketUK/EU
Manufacturer noise reference at 7 m76 dB(A)

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load61 litres/hour
75% Load90 litres/hour
100% Load123 litres/hour
110% Load134 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.

Compare your options

Related generators.

Let’s specify your next generator.

Tell us your load, site and application. We’ll help you choose the right configuration.

Talk to GenPro
Call GenProRequest a quote