GENPRO / UK DESIGNED & MANUFACTURED GENERATORS+44 (0)121 517 0315
GENPRO / OPEN SETGPS560PPerkins · 2506A-E15TAG2Build-specific image supplied with quotation

A model-specific render and installation drawing will be supplied with the quotation.

Perkins engine manufacturer logo
Designed and manufactured in the United KingdomDesigned and manufactured
in the United Kingdom
Perkins / Open set / 50 Hz

560 kVA class
Perkins diesel generator

GPS560P

Open set generator with a 2506A-E15TAG2 engine and Stamford S5L1D-D41 reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.

Prime / PRP513 kVA410 kW
Standby / ESP562 kVA450 kW

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS560P
Engine brand / modelPerkins 2506A-E15TAG2
AlternatorStamford S5L1D-D41
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating513 kVA / 410 kW
Exact standby rating562 kVA / 450 kW
AspirationTurbocharged
GovernorElectronic
No. of Cylinders6
Cylinder ArrangementIn Line
Displacement15.2L
Cooling TypeLiquid Cooled
Coolant Capacity58.0L
Oil Capacity62.0L
TypeBrushless
Poles4
AVR ModelAS440
Voltage Regulation1.0% Regulation%
Insulation ClassH
ExcitationBrushless

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
380 V550 kVA440 kW500 kVA400 kW
400 V562 kVA450 kW513 kVA410 kW
415 V550 kVA440 kW500 kVA400 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
2506A-E15TAG2Stamford S5L1D-D413400 V513 kVA562 kVA

Installation & enclosure

Dimensions (L × W × H)3499 × 1273 × 2057 mm
Reference weight3637.7 kg
Reference fuel tank590 litres
Configuration marketUK/EU

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load53 litres/hour
75% Load76 litres/hour
100% Load100 litres/hour
110% Load111 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.

Compare your options

Related generators.

Let’s specify your next generator.

Tell us your load, site and application. We’ll help you choose the right configuration.

Talk to GenPro