GENPRO / UK DESIGNED & MANUFACTURED GENERATORS+44 (0)121 517 0315
GENPRO / OPEN SETGPS500SScania · DC13072A-02-13Build-specific image supplied with quotation

A model-specific render and installation drawing will be supplied with the quotation.

Scania engine manufacturer logo
Designed and manufactured in the United KingdomDesigned and manufactured
in the United Kingdom
Scania / Open set / 50 Hz

500 kVA class
Scania diesel generator

GPS500S

Open set generator with a DC13072A-02-13 engine and Stamford HCI544C1 reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.

Prime / PRP461 kVA369 kW
Standby / ESP501 kVA401 kW

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS500S
Engine brand / modelScania DC13072A-02-13
AlternatorStamford HCI544C1
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating461 kVA / 369 kW
Exact standby rating501 kVA / 401 kW
AspirationTurbocharged
GovernorECU
No. of Cylinders6
Cylinder ArrangementIn Line
Displacement12.7L
Cooling TypeLiquid Cooled
Coolant Capacity38L
Oil Capacity36L
TypeBrushless
Poles4
AVR ModelAS440
Voltage Regulation1%
Insulation ClassH
ExcitationSelf Excited

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
190 V500 kVA400 kW455 kVA364 kW
200 V501 kVA401 kW461 kVA369 kW
208 V500 kVA400 kW455 kVA364 kW
220 V495 kVA396 kW450 kVA360 kW
220 V500 kVA400 kW455 kVA364 kW
230 V501 kVA401 kW461 kVA369 kW
240 V500 kVA400 kW455 kVA364 kW
254 V495 kVA396 kW450 kVA360 kW
380 V500 kVA400 kW455 kVA364 kW
400 V501 kVA401 kW461 kVA369 kW
415 V500 kVA400 kW455 kVA364 kW
440 V495 kVA396 kW450 kVA360 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
DC13072A-02-13Stamford HCI544C13400 V461 kVA501 kVA
DC13072A-02-13Stamford S4L1D-G413400 V450 kVA496 kVA
DC16071A-02-01Stamford S5L1D-D413400 V501 kVAConfirm on enquiry

Installation & enclosure

Reference weight2788.2 kg
Reference fuel tank730 litres
Configuration marketExport

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load43.9 litres/hour
75% Load65.1 litres/hour
100% Load88.2 litres/hour
110% Load98.9 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.

Compare your options

Related generators.

Let’s specify your next generator.

Tell us your load, site and application. We’ll help you choose the right configuration.

Talk to GenPro
Call GenProRequest a quote