A model-specific render and installation drawing will be supplied with the quotation.
Designed and manufacturedin the United KingdomPerkins / Open set / 50 Hz
460 kVA class
Perkins diesel generator
Open set generator with a 2206A-E13TAG3 engine and Stamford S4L1D-F41 reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.
Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.
Price and lead time confirmed with your quotation.
Technical specification.
| GenPro model | GPS460P |
|---|---|
| Engine brand / model | Perkins 2206A-E13TAG3 |
| Alternator | Stamford S4L1D-F41 |
| Frequency | 50 Hz |
| Reference voltage | 400 V |
| Reference phase | 3 phase |
| Exact prime rating | 406 kVA / 325 kW |
| Exact standby rating | 454 kVA / 363 kW |
| Aspiration | Turbocharged |
|---|---|
| Governor | Electronic |
| No. of Cylinders | 6 |
| Cylinder Arrangement | In Line |
| Displacement | 12.5L |
| Cooling Type | Liquid Cooled |
| Coolant Capacity | 51.4L |
| Oil Capacity | 40.0L |
| Type | Brushless |
| Poles | 4 |
| AVR Model | AS440 |
| Voltage Regulation | 1% |
| Insulation Class | H |
| Excitation | Self Excited |
Voltage-specific ratings
Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.
| Voltage | ESP kVA | ESP kW | PRP kVA | PRP kW |
|---|---|---|---|---|
| 190 V | 425 kVA | 340 kW | 400 kVA | 320 kW |
| 200 V | 454 kVA | 363 kW | 406 kVA | 325 kW |
| 208 V | 455 kVA | 364 kW | 407 kVA | 326 kW |
| 220 V | 440 kVA | 352 kW | 400 kVA | 320 kW |
| 220 V | 425 kVA | 340 kW | 400 kVA | 320 kW |
| 230 V | 454 kVA | 363 kW | 406 kVA | 325 kW |
| 240 V | 455 kVA | 364 kW | 407 kVA | 326 kW |
| 254 V | 440 kVA | 352 kW | 400 kVA | 320 kW |
| 380 V | 425 kVA | 340 kW | 400 kVA | 320 kW |
| 400 V | 454 kVA | 363 kW | 406 kVA | 325 kW |
| 415 V | 455 kVA | 364 kW | 407 kVA | 326 kW |
| 440 V | 440 kVA | 352 kW | 400 kVA | 320 kW |
Configuration options.
These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.
| Engine | Alternator | Phase | Voltage | Prime / PRP | Standby / ESP |
|---|---|---|---|---|---|
| 2206A-E13TAG3 | Stamford S4L1D-F41 | 3 | 400 V | 406 kVA | 454 kVA |
Installation & enclosure
| Dimensions (L × W × H) | 3272 × 1180 × 2057 mm |
|---|---|
| Reference weight | 3166.1 kg |
| Reference fuel tank | 730 litres |
| Configuration market | Export |
Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.
Fuel consumption
| 50% Load | 42 litres/hour |
|---|---|
| 75% Load | 62 litres/hour |
| 100% Load | 81 litres/hour |
| 110% Load | 90 litres/hour |
Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.