GENPRO / UK DESIGNED & MANUFACTURED GENERATORS+44 (0)121 517 0315
Baudouin acoustic canopied generator — representative configuration image

Representative generator image; final appearance follows the confirmed build specification.

Baudouin engine manufacturer logo
Designed and manufactured in the United KingdomDesigned and manufactured
in the United Kingdom
Baudouin / Acoustic canopied / 50 Hz

440 kVA class
Baudouin diesel generator

GPS440BS

Acoustic canopied generator with a 6M21G440/5 engine and Stamford S4L1D-F41 reference alternator. Acoustic canopy and sound requirements to be confirmed for your application.

Prime / PRP402 kVA322 kW
Standby / ESP442 kVA354 kW

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS440BS
Engine brand / modelBaudouin 6M21G440/5
AlternatorStamford S4L1D-F41
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating402 kVA / 322 kW
Exact standby rating442 kVA / 354 kW
AspirationTurbocharged
GovernorElectronic
No. of Cylinders6
Cylinder ArrangementIn Line
Displacement12.54L
Cooling TypeLiquid Cooled
Coolant Capacity47L
Oil Capacity40L
TypeBrushless
Poles4
AVR ModelAS440
Voltage Regulation1%
Insulation ClassH
ExcitationSelf Excited

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
190 V425 kVA340 kW400 kVA320 kW
200 V442 kVA354 kW402 kVA322 kW
208 V444 kVA355 kW403 kVA322 kW
220 V440 kVA352 kW400 kVA320 kW
220 V425 kVA340 kW400 kVA320 kW
230 V442 kVA354 kW402 kVA322 kW
240 V444 kVA355 kW403 kVA322 kW
254 V440 kVA352 kW400 kVA320 kW
380 V425 kVA340 kW400 kVA320 kW
400 V442 kVA354 kW402 kVA322 kW
415 V444 kVA355 kW403 kVA322 kW
440 V440 kVA352 kW400 kVA320 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
6M21G440/5Stamford S4L1D-F413400 V402 kVA442 kVA
6M21G440/5KWise C314G3203400 V400 kVA440 kVA
6M21G440/5Leroy Somer TAL0473A3400 V402 kVA443 kVA

Installation & enclosure

Dimensions (L × W × H)3958 × 1504 × 2384 mm
Reference weight3696.5 kg
Reference fuel tank500 litres
Configuration marketUK/EU
Manufacturer noise reference at 7 m76 dB(A)

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load43.2 litres/hour
75% Load63.5 litres/hour
100% Load85.5 litres/hour
110% Load94.8 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.

Compare your options

Related generators.

Let’s specify your next generator.

Tell us your load, site and application. We’ll help you choose the right configuration.

Talk to GenPro
Call GenProRequest a quote