GENPRO / UK DESIGNED & MANUFACTURED GENERATORS+44 (0)121 517 0315
GENPRO / OPEN SETGPS350PPerkins · 1506A-E88TAG5Build-specific image supplied with quotation

A model-specific render and installation drawing will be supplied with the quotation.

Perkins engine manufacturer logo
Designed and manufactured in the United KingdomDesigned and manufactured
in the United Kingdom
Perkins / Open set / 50 Hz

350 kVA class
Perkins diesel generator

GPS350P

Open set generator with a 1506A-E88TAG5 engine and KWise C314G320 reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.

Prime / PRP316 kVA253 kW
Standby / ESP347 kVA278 kW

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS350P
Engine brand / modelPerkins 1506A-E88TAG5
AlternatorKWise C314G320
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating316 kVA / 253 kW
Exact standby rating347 kVA / 278 kW
AspirationTurbocharged
GovernorElectronic
No. of Cylinders6
Cylinder ArrangementIn Line
Displacement8.8L
Cooling TypeLiquid Cooled
Coolant Capacity33.2L
Oil Capacity41.0L
TypeBrushless
Poles4
AVR ModelSX440
Voltage Regulation1%
Insulation ClassH
ExcitationPMG

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
200 V347 kVA278 kW316 kVA253 kW
230 V347 kVA278 kW316 kVA253 kW
400 V347 kVA278 kW316 kVA253 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
1506A-E88TAG5KWise C314G3203400 V316 kVA347 kVA

Installation & enclosure

Dimensions, weight and fuel tankConfirmed with quotation and build drawing

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load33 litres/hour
75% Load48.2 litres/hour
100% Load64.9 litres/hour
110% Load73.1 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.

Compare your options

Related generators.

Let’s specify your next generator.

Tell us your load, site and application. We’ll help you choose the right configuration.

Talk to GenPro
Call GenProRequest a quote