GENPRO / UK DESIGNED & MANUFACTURED GENERATORS+44 (0)121 517 0315
GENPRO / OPEN SETGPS310SScania · DC09072A-02-12Build-specific image supplied with quotation

A model-specific render and installation drawing will be supplied with the quotation.

Scania engine manufacturer logo
Designed and manufactured in the United KingdomDesigned and manufactured
in the United Kingdom
Scania / Open set / 50 Hz

310 kVA class
Scania diesel generator

GPS310S

Open set generator with a DC09072A-02-12 engine and Stamford S4L1D-D41 reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.

Prime / PRP281 kVA225 kW
Standby / ESP308 kVA246 kW

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS310S
Engine brand / modelScania DC09072A-02-12
AlternatorStamford S4L1D-D41
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating281 kVA / 225 kW
Exact standby rating308 kVA / 246 kW
AspirationTurbocharged
GovernorECU
No. of Cylinders5
Cylinder ArrangementIn Line
Displacement9.3L
Cooling TypeLiquid Cooled
Coolant Capacity37L
Oil Capacity36L
TypeBrushless
Poles4
AVR ModelAS440
Voltage Regulation1%
Insulation ClassH
ExcitationSelf Excited

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
190 V307 kVA246 kW282 kVA226 kW
200 V308 kVA246 kW281 kVA225 kW
208 V309 kVA247 kW282 kVA226 kW
220 V311 kVA249 kW283 kVA226 kW
220 V307 kVA246 kW280 kVA224 kW
230 V308 kVA246 kW281 kVA225 kW
240 V309 kVA247 kW282 kVA226 kW
254 V311 kVA249 kW283 kVA226 kW
380 V307 kVA246 kW280 kVA224 kW
400 V308 kVA246 kW281 kVA225 kW
415 V309 kVA247 kW282 kVA226 kW
440 V311 kVA249 kW283 kVA226 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
DC09072A-02-12Stamford S4L1D-D413400 V281 kVA308 kVA
DC09071A-02-04Stamford S4L1D-D413400 V310 kVAConfirm on enquiry

Installation & enclosure

Reference weight2359.15 kg
Reference fuel tank730 litres
Configuration marketExport

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load28.3 litres/hour
75% Load41.1 litres/hour
100% Load56 litres/hour
110% Load63 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.

Compare your options

Related generators.

Let’s specify your next generator.

Tell us your load, site and application. We’ll help you choose the right configuration.

Talk to GenPro
Call GenProRequest a quote