A model-specific render and installation drawing will be supplied with the quotation.
Designed and manufacturedin the United KingdomPerkins / Open set / 50 Hz
310 kVA class
Perkins diesel generator
Open set generator with a 1506A-E88TAG4 engine and Stamford S4L1D-D41 reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.
Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.
Price and lead time confirmed with your quotation.
Technical specification.
| GenPro model | GPS310P |
|---|---|
| Engine brand / model | Perkins 1506A-E88TAG4 |
| Alternator | Stamford S4L1D-D41 |
| Frequency | 50 Hz |
| Reference voltage | 400 V |
| Reference phase | 3 phase |
| Exact prime rating | 283 kVA / 226 kW |
| Exact standby rating | 308 kVA / 246 kW |
| Aspiration | Turbocharged |
|---|---|
| Governor | Electronic |
| No. of Cylinders | 6 |
| Cylinder Arrangement | In Line |
| Displacement | 8.8L |
| Cooling Type | Liquid Cooled |
| Coolant Capacity | 33.2L |
| Oil Capacity | 41.0L |
| Type | Brushless |
| Poles | 4 |
| AVR Model | AS440 |
| Voltage Regulation | 1% |
| Insulation Class | H |
| Excitation | Self Excited |
Voltage-specific ratings
Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.
| Voltage | ESP kVA | ESP kW | PRP kVA | PRP kW |
|---|---|---|---|---|
| 190 V | 307 kVA | 246 kW | 284 kVA | 227 kW |
| 200 V | 308 kVA | 246 kW | 283 kVA | 226 kW |
| 208 V | 309 kVA | 247 kW | 284 kVA | 227 kW |
| 220 V | 311 kVA | 249 kW | 285 kVA | 228 kW |
| 220 V | 307 kVA | 246 kW | 283 kVA | 226 kW |
| 230 V | 308 kVA | 246 kW | 283 kVA | 226 kW |
| 240 V | 309 kVA | 247 kW | 284 kVA | 227 kW |
| 254 V | 311 kVA | 249 kW | 285 kVA | 228 kW |
| 380 V | 307 kVA | 246 kW | 283 kVA | 226 kW |
| 400 V | 308 kVA | 246 kW | 283 kVA | 226 kW |
| 415 V | 309 kVA | 247 kW | 284 kVA | 227 kW |
| 440 V | 311 kVA | 249 kW | 285 kVA | 228 kW |
Configuration options.
These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.
| Engine | Alternator | Phase | Voltage | Prime / PRP | Standby / ESP |
|---|---|---|---|---|---|
| 1506A-E88TAG4 | Stamford S4L1D-D41 | 3 | 400 V | 283 kVA | 308 kVA |
Installation & enclosure
| Reference weight | 2600.65 kg |
|---|---|
| Reference fuel tank | 730 litres |
| Configuration market | Export |
Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.
Fuel consumption
| 50% Load | 31.6 litres/hour |
|---|---|
| 75% Load | 45.8 litres/hour |
| 100% Load | 60.2 litres/hour |
| 110% Load | 66.3 litres/hour |
Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.