GENPRO / UK DESIGNED & MANUFACTURED GENERATORS+44 (0)121 517 0315
GENPRO / OPEN SETGPS270PPerkins · 1206A-E70TTAG3Build-specific image supplied with quotation

A model-specific render and installation drawing will be supplied with the quotation.

Perkins engine manufacturer logo
Designed and manufactured in the United KingdomDesigned and manufactured
in the United Kingdom
Perkins / Open set / 50 Hz

270 kVA class
Perkins diesel generator

GPS270P

Open set generator with a 1206A-E70TTAG3 engine and Leroy Somer TAL046D reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.

Prime / PRP248 kVA198 kW
Standby / ESP270 kVA216 kW

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS270P
Engine brand / modelPerkins 1206A-E70TTAG3
AlternatorLeroy Somer TAL046D
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating248 kVA / 198 kW
Exact standby rating270 kVA / 216 kW
AspirationTurbocharged
GovernorElectronic
No. of Cylinders6
Cylinder ArrangementIn Line
Displacement7.01L
Cooling TypeLiquid Cooled
Coolant Capacity25.0L
Oil Capacity16.0L
TypeBrushless
Poles4
AVR ModelR150
Voltage Regulation1%
Insulation ClassH
ExcitationSelf Excited

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
400 V270 kVA216 kW248 kVA198 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
1206A-E70TTAG3Leroy Somer TAL046D3400 V248 kVA270 kVA

Installation & enclosure

Dimensions (L × W × H)3000 × 1000 × 1767 mm
Reference weight1825.6 kg
Reference fuel tank730 litres
Configuration marketExport

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load28.1 litres/hour
75% Load41.5 litres/hour
100% Load56.9 litres/hour
110% Load64.5 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.

Compare your options

Related generators.

Let’s specify your next generator.

Tell us your load, site and application. We’ll help you choose the right configuration.

Talk to GenPro
Call GenProRequest a quote