2,050 kVA class
Cummins generator
QSK60G3 HPI
A model-specific render and installation drawing will be supplied with the quotation.
Designed and manufacturedOpen set generator with a QSK60G3 HPI engine and Stamford S7L1D-G41 reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.
Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.
Price and lead time confirmed with your quotation.
| GenPro model | GPS2050C |
|---|---|
| Engine brand / model | Cummins QSK60G3 HPI |
| Alternator | Stamford S7L1D-G41 |
| Frequency | 50 Hz |
| Reference voltage | 400 V |
| Reference phase | 3 phase |
| Exact prime rating | 1876 kVA / 1501 kW |
| Exact standby rating | 2061 kVA / 1649 kW |
| Aspiration | Turbocharged |
|---|---|
| Governor | Electronic |
| No. of Cylinders | 16 |
| Cylinder Arrangement | At Vee |
| Displacement | 60.2L |
| Cooling Type | Liquid Cooled |
| Coolant Capacity | 490L |
| Oil Capacity | 280L |
| Type | Brushless |
| Poles | 4 |
| AVR Model | MX341 |
| Voltage Regulation | 1% |
| Insulation Class | H |
| Excitation | PMG |
Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.
| Voltage | ESP kVA | ESP kW | PRP kVA | PRP kW |
|---|---|---|---|---|
| 380 V | 2061 kVA | 1649 kW | 1876 kVA | 1501 kW |
| 400 V | 2061 kVA | 1649 kW | 1876 kVA | 1501 kW |
These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.
| Engine | Alternator | Phase | Voltage | Prime / PRP | Standby / ESP |
|---|---|---|---|---|---|
| QSK60G3 HPI | Stamford S7L1D-G41 | 3 | 400 V | 1876 kVA | 2061 kVA |
| QSK60G3 HPI | Stamford S7L1D-F41 | 3 | 400 V | 1872 kVA | 2035 kVA |
| Dimensions, weight and fuel tank | Confirmed with quotation and build drawing |
|---|
Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.
| 50% Load | 190 litres/hour |
|---|---|
| 75% Load | 270 litres/hour |
| 100% Load | 363 litres/hour |
| 110% Load | 406 litres/hour |
Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.
QSK60G3 HPI
QSK60G4 HPI
Tell us your load, site and application. We’ll help you choose the right configuration.