GENPRO / UK DESIGNED & MANUFACTURED GENERATORS+44 (0)121 517 0315
GENPRO / ACOUSTIC CANOPIEDGPS2050BSBaudouin · 16M33G2000/5Build-specific image supplied with quotation

A model-specific render and installation drawing will be supplied with the quotation.

Baudouin engine manufacturer logo
Designed and manufactured in the United KingdomDesigned and manufactured
in the United Kingdom
Baudouin / Acoustic canopied / 50 Hz

2,050 kVA class
Baudouin diesel generator

GPS2050BS

Acoustic canopied generator with a 16M33G2000/5 engine and Stamford S7L1D-F41 reference alternator. Acoustic canopy and sound requirements to be confirmed for your application.

Prime / PRP1900 kVA1520 kW
Standby / ESP2035 kVA1628 kW

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS2050BS
Engine brand / modelBaudouin 16M33G2000/5
AlternatorStamford S7L1D-F41
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating1900 kVA / 1520 kW
Exact standby rating2035 kVA / 1628 kW
AspirationTurbocharged
GovernorECU
No. of Cylinders16
Cylinder ArrangementAt Vee
Displacement52.3L
Cooling TypeLiquid Cooled
Coolant Capacity400L
Oil Capacity175L
TypeBrushless
Poles4
AVR ModelMX341
Voltage Regulation1%
Insulation ClassH
ExcitationPMG

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
380 V1975 kVA1580 kW1845 kVA1476 kW
400 V2035 kVA1628 kW1900 kVA1520 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
16M33G2000/5Stamford S7L1D-F413400 V1900 kVA2035 kVA
16M33G2250/5Stamford S7L1D-F413400 V1900 kVA2035 kVA

Installation & enclosure

Dimensions, weight and fuel tankConfirmed with quotation and build drawing

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load194.7 litres/hour
75% Load290.7 litres/hour
100% Load401 litres/hour
110% Load446.8 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.

Compare your options

Related generators.

Let’s specify your next generator.

Tell us your load, site and application. We’ll help you choose the right configuration.

Talk to GenPro
Call GenProRequest a quote