Perkins / Acoustic canopied / 50 Hz

2,000 kVA class
Perkins diesel generator

GPS2000PS

Acoustic canopied generator with a 4016-61TRG1 engine and Stamford S7L1D-F41 reference alternator. Acoustic canopy and sound requirements to be confirmed for your application.

Prime / PRP1866 kVA1493 kW
Standby / ESP2012 kVA1610 kW

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS2000PS
Engine brand / modelPerkins 4016-61TRG1
AlternatorStamford S7L1D-F41
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating1866 kVA / 1493 kW
Exact standby rating2012 kVA / 1610 kW
AspirationTurbocharged
GovernorElectronic
No. of Cylinders16
Cylinder ArrangementAt Vee
Displacement61.123L
Cooling TypeLiquid Cooled
Coolant Capacity170L
Oil Capacity213L
TypeBrushless
Poles4
AVR ModelMX341
Voltage Regulation1%
Insulation ClassH
ExcitationPMG

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
380 V1975 kVA1580 kW1845 kVA1476 kW
400 V2012 kVA1610 kW1866 kVA1493 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
4016-61TRG1Stamford S7L1D-F413400 V1866 kVA2012 kVA
4016-61TRG1Leroy Somer LSA52.3S53400 V1860 kVA2018 kVA

Installation & enclosure

Dimensions, weight and fuel tankConfirmed with quotation and build drawing

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load193 litres/hour
75% Load280 litres/hour
100% Load371 litres/hour
110% Load401 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.