GENPRO / UK DESIGNED & MANUFACTURED GENERATORS+44 (0)121 517 0315
Perkins acoustic canopied generator — representative configuration image

GenPro-branded enclosure reference; final appearance follows the confirmed build specification.

Perkins engine manufacturer logo
Designed and manufactured in the United KingdomDesigned and manufactured
in the United Kingdom
Perkins / Acoustic canopied / 50 Hz

200 kVA class
Perkins diesel generator

GPS200PS

Acoustic canopied generator with a 1106A-70TAG3 engine and Stamford UCI274H1 reference alternator. Acoustic canopy and sound requirements to be confirmed for your application.

Prime / PRP184 kVA147 kW
Standby / ESP204 kVA163 kW

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS200PS
Engine brand / modelPerkins 1106A-70TAG3
AlternatorStamford UCI274H1
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating184 kVA / 147 kW
Exact standby rating204 kVA / 163 kW
AspirationTurbocharged
GovernorMechanical
No. of Cylinders6
Cylinder ArrangementIn Line
Displacement7.01L
Cooling TypeLiquid Cooled
Coolant Capacity21.0L
Oil Capacity18.0L
TypeBrushless
Poles4
AVR ModelAS440
Voltage Regulation1%
Insulation ClassH
ExcitationSelf Excited

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
190 V203 kVA162 kW182 kVA146 kW
200 V204 kVA163 kW184 kVA147 kW
208 V204 kVA163 kW184 kVA147 kW
220 V203 kVA162 kW183 kVA146 kW
230 V204 kVA163 kW184 kVA147 kW
240 V204 kVA163 kW184 kVA147 kW
380 V203 kVA162 kW183 kVA146 kW
400 V204 kVA163 kW184 kVA147 kW
415 V204 kVA163 kW184 kVA147 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
1106A-70TAG3Stamford UCI274H13400 V184 kVA204 kVA
1106A-70TAG3Leroy Somer TAL044L3400 V180 kVA200 kVA

Installation & enclosure

Dimensions (L × W × H)3208 × 1164 × 1778 mm
Reference weight2413.85 kg
Reference fuel tank325 litres
Configuration marketUK/EU
Manufacturer noise reference at 7 m76 dB(A)

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load20.2 litres/hour
75% Load32 litres/hour
100% Load41.4 litres/hour
110% Load45.1 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.

Compare your options

Related generators.

Let’s specify your next generator.

Tell us your load, site and application. We’ll help you choose the right configuration.

Talk to GenPro
Call GenProRequest a quote