GENPRO / UK DESIGNED & MANUFACTURED GENERATORS+44 (0)121 517 0315
Perkins acoustic canopied generator — representative configuration image

GenPro-branded enclosure reference; final appearance follows the confirmed build specification.

Perkins engine manufacturer logo
Designed and manufactured in the United KingdomDesigned and manufactured
in the United Kingdom
Perkins / Acoustic canopied / 50 Hz

20 kVA class
Perkins diesel generator

GPS20PS

Acoustic canopied generator with a 404A-22G engine and Stamford S0L2-G1 reference alternator. Acoustic canopy and sound requirements to be confirmed for your application.

Prime / PRP19.6 kVA15.7 kW
Standby / ESP21.2 kVA17 kW

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS20PS
Engine brand / modelPerkins 404A-22G
AlternatorStamford S0L2-G1
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating19.6 kVA / 15.7 kW
Exact standby rating21.2 kVA / 17 kW
AspirationNaturally Aspirated
GovernorMechanical
No. of Cylinders4
Cylinder ArrangementIn Line
Displacement2.216L
Cooling TypeLiquid Cooled
Coolant Capacity7.0L
Oil Capacity10.6L
TypeBrushless
Poles4
AVR ModelAS540
Voltage Regulation1%
Insulation ClassH
ExcitationSelf Excited

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
200 V21.2 kVA17 kW19.6 kVA15.7 kW
208 V21.3 kVA17 kW19.7 kVA15.8 kW
230 V21.2 kVA17 kW19.6 kVA15.7 kW
240 V21.3 kVA17 kW19.7 kVA15.8 kW
400 V21.2 kVA17 kW19.6 kVA15.7 kW
415 V21.3 kVA17 kW19.7 kVA15.8 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
404A-22GStamford S0L2-G13400 V19.6 kVA21.2 kVA
404J-22GStamford S0L2-G13400 V19.7 kVA21.4 kVA
403A-15G2Stamford S0L2-G13400 V14.8 kVA15.9 kVA
404A-22GLeroy Somer TAL040F3400 V20 kVA22 kVA
404J-22GLeroy Somer TAL040F3400 V20 kVA22 kVA
403A-15G2Leroy Somer TAL040D3400 V14.8 kVA16.2 kVA
404A-22GStamford S1L2-J11230 V18.3 kVA20.1 kVA
404J-22GStamford S1L2-J11230 V18.4 kVA20.3 kVA
403A-15G2Stamford S1L2-J11230 V13.8 kVA15.1 kVA
404A-22GLeroy Somer TAL042D1230 V18.5 kVA20.2 kVA
404J-22GLeroy Somer TAL042D1230 V18.6 kVA20.4 kVA
404A-22GLeroy Somer TAL042C1230 V18 kVA19.5 kVA

Installation & enclosure

Dimensions (L × W × H)2240 × 1038 × 1378 mm
Reference weight880.75 kg
Reference fuel tank80 litres
Configuration marketUK/EU
Manufacturer noise reference at 7 m76 dB(A)

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load2.9 litres/hour
75% Load4 litres/hour
100% Load5.3 litres/hour
110% Load6.1 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.

Compare your options

Related generators.

Let’s specify your next generator.

Tell us your load, site and application. We’ll help you choose the right configuration.

Talk to GenPro
Call GenProRequest a quote