GENPRO / UK DESIGNED & MANUFACTURED GENERATORS+44 (0)121 517 0315
GENPRO / OPEN SETGPS20BBaudouin · 4M06G2D0/SBuild-specific image supplied with quotation

A model-specific render and installation drawing will be supplied with the quotation.

Baudouin engine manufacturer logo
Designed and manufactured in the United KingdomDesigned and manufactured
in the United Kingdom
Baudouin / Open set / 50 Hz

20 kVA class
Baudouin diesel generator

GPS20B

Open set generator with a 4M06G2D0/S engine and Stamford S0L2-G1 reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.

Prime / PRP17.8 kVA14.2 kW
Standby / ESP19.6 kVA15.7 kW

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS20B
Engine brand / modelBaudouin 4M06G2D0/S
AlternatorStamford S0L2-G1
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating17.8 kVA / 14.2 kW
Exact standby rating19.6 kVA / 15.7 kW
AspirationNaturally Aspirated
GovernorElectronic
No. of Cylinders4
Cylinder ArrangementIn Line
Displacement2.3L
Cooling TypeLiquid Cooled
Coolant Capacity8.6L
Oil Capacity11.5L
TypeBrushless
Poles4
AVR ModelAS540
Voltage Regulation1%
Insulation ClassH
ExcitationSelf Excited

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
200 V19.6 kVA15.7 kW17.8 kVA14.2 kW
208 V19.6 kVA15.7 kW17.8 kVA14.2 kW
230 V19.6 kVA15.7 kW17.8 kVA14.2 kW
240 V19.6 kVA15.7 kW17.8 kVA14.2 kW
400 V19.6 kVA15.7 kW17.8 kVA14.2 kW
415 V19.6 kVA15.7 kW17.8 kVA14.2 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
4M06G2D0/SStamford S0L2-G13400 V17.8 kVA19.6 kVA
4M06G2D0/SStamford S1L2-J11230 V16.6 kVA18.5 kVA
4M06G4D0/SStamford S1L2-N11230 V21.8 kVA23.7 kVA
4M06G4D0/SLeroy Somer TAL042C1230 V19 kVA21 kVA

Installation & enclosure

Dimensions, weight and fuel tankConfirmed with quotation and build drawing

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load2.6 litres/hour
75% Load3.6 litres/hour
100% Load4.7 litres/hour
110% Load5.2 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.

Compare your options

Related generators.

Let’s specify your next generator.

Tell us your load, site and application. We’ll help you choose the right configuration.

Talk to GenPro
Call GenProRequest a quote