A model-specific render and installation drawing will be supplied with the quotation.
Designed and manufacturedin the United KingdomCummins / Open set / 50 Hz
170 kVA class
Cummins diesel generator
Open set generator with a 6BTAA5.9G7 engine and Stamford UCI274F1 reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.
Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.
Price and lead time confirmed with your quotation.
Technical specification.
| GenPro model | GPS170C |
|---|---|
| Engine brand / model | Cummins 6BTAA5.9G7 |
| Alternator | Stamford UCI274F1 |
| Frequency | 50 Hz |
| Reference voltage | 400 V |
| Reference phase | 3 phase |
| Exact prime rating | 154 kVA / 123 kW |
| Exact standby rating | 169 kVA / 135 kW |
| Aspiration | Turbocharged |
|---|---|
| Governor | Electronic |
| No. of Cylinders | 6 |
| Cylinder Arrangement | In Line |
| Displacement | 5.9L |
| Cooling Type | Liquid Cooled |
| Coolant Capacity | 9.1L |
| Oil Capacity | 16.4 |
| Type | Brushless |
| Poles | 4 |
| AVR Model | AS440 |
| Voltage Regulation | 1% |
| Insulation Class | H |
| Excitation | Self Excited |
Voltage-specific ratings
Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.
| Voltage | ESP kVA | ESP kW | PRP kVA | PRP kW |
|---|---|---|---|---|
| 190 V | 168 kVA | 134 kW | 154 kVA | 123 kW |
| 200 V | 169 kVA | 135 kW | 154 kVA | 123 kW |
| 208 V | 170 kVA | 136 kW | 155 kVA | 124 kW |
| 220 V | 168 kVA | 134 kW | 154 kVA | 123 kW |
| 230 V | 169 kVA | 135 kW | 154 kVA | 123 kW |
| 240 V | 170 kVA | 136 kW | 155 kVA | 124 kW |
| 380 V | 168 kVA | 134 kW | 154 kVA | 123 kW |
| 400 V | 169 kVA | 135 kW | 154 kVA | 123 kW |
| 415 V | 170 kVA | 136 kW | 155 kVA | 124 kW |
Configuration options.
These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.
| Engine | Alternator | Phase | Voltage | Prime / PRP | Standby / ESP |
|---|---|---|---|---|---|
| 6BTAA5.9G7 | Stamford UCI274F1 | 3 | 400 V | 154 kVA | 169 kVA |
Installation & enclosure
| Reference weight | 1507.65 kg |
|---|---|
| Reference fuel tank | 310 litres |
| Configuration market | Export |
Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.
Fuel consumption
| 50% Load | 19 litres/hour |
|---|---|
| 75% Load | 29 litres/hour |
| 100% Load | 37 litres/hour |
| 110% Load | 41 litres/hour |
Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.