GENPRO / UK DESIGNED & MANUFACTURED GENERATORS+44 (0)121 517 0315
GENPRO / OPEN SETGPS1500PPerkins · 4012-46TWG3ABuild-specific image supplied with quotation

A model-specific render and installation drawing will be supplied with the quotation.

Perkins engine manufacturer logo
Designed and manufactured in the United KingdomDesigned and manufactured
in the United Kingdom
Perkins / Open set / 50 Hz

1,500 kVA class
Perkins diesel generator

GPS1500P

Open set generator with a 4012-46TWG3A engine and Leroy Somer LSA50.2L7 reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.

Prime / PRP1350 kVA1080 kW
Standby / ESP1485 kVA1188 kW

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS1500P
Engine brand / modelPerkins 4012-46TWG3A
AlternatorLeroy Somer LSA50.2L7
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating1350 kVA / 1080 kW
Exact standby rating1485 kVA / 1188 kW
AspirationTurbocharged
GovernorElectronic
No. of Cylinders12
Cylinder ArrangementAt Vee
Displacement45.84L
Cooling TypeLiquid Cooled
Coolant Capacity173L
Oil Capacity157.5L
TypeBrushless
Poles4
AVR ModelD350
Voltage Regulation0.5%
Insulation ClassH
ExcitationAuxiliary Wound

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
400 V1485 kVA1188 kW1350 kVA1080 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
4012-46TWG3ALeroy Somer LSA50.2L73400 V1350 kVA1485 kVA
4012-46TWG3AStamford S6L1D-H413400 V1364 kVA1497 kVA
4012-46TAG1AStamford S6L1D-H413400 V1363 kVA1497 kVA
4012-46TAG1ALeroy Somer LSA50.2L73400 V1350 kVA1485 kVA

Installation & enclosure

Dimensions (L × W × H)4725 × 1920 × 2543 mm
Reference weight9255.75 kg
Configuration marketExport

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load142.6 litres/hour
75% Load207.5 litres/hour
100% Load280.9 litres/hour
110% Load315.1 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.