A model-specific render and installation drawing will be supplied with the quotation.
Designed and manufacturedin the United KingdomBaudouin / Open set / 50 Hz
150 kVA class
Baudouin diesel generator
Open set generator with a 6M11G2D0/S engine and Stamford UCI274E1 reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.
Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.
Price and lead time confirmed with your quotation.
Technical specification.
| GenPro model | GPS150B |
|---|---|
| Engine brand / model | Baudouin 6M11G2D0/S |
| Alternator | Stamford UCI274E1 |
| Frequency | 50 Hz |
| Reference voltage | 400 V |
| Reference phase | 3 phase |
| Exact prime rating | 132 kVA / 106 kW |
| Exact standby rating | 145 kVA / 116 kW |
| Aspiration | Turbocharged |
|---|---|
| Governor | Electronic |
| No. of Cylinders | 6 |
| Cylinder Arrangement | In Line |
| Displacement | 6.75L |
| Cooling Type | Liquid Cooled |
| Coolant Capacity | 20L |
| Oil Capacity | 19L |
| Type | Brushless |
| Poles | 4 |
| AVR Model | AS440 |
| Voltage Regulation | 1% |
| Insulation Class | H |
| Excitation | Self Excited |
Voltage-specific ratings
Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.
| Voltage | ESP kVA | ESP kW | PRP kVA | PRP kW |
|---|---|---|---|---|
| 190 V | 144 kVA | 115 kW | 132 kVA | 106 kW |
| 200 V | 145 kVA | 116 kW | 132 kVA | 106 kW |
| 208 V | 146 kVA | 117 kW | 132 kVA | 106 kW |
| 220 V | 144 kVA | 115 kW | 131 kVA | 105 kW |
| 230 V | 145 kVA | 116 kW | 132 kVA | 106 kW |
| 240 V | 146 kVA | 117 kW | 132 kVA | 106 kW |
| 380 V | 144 kVA | 115 kW | 131 kVA | 105 kW |
| 400 V | 145 kVA | 116 kW | 132 kVA | 106 kW |
| 415 V | 146 kVA | 117 kW | 132 kVA | 106 kW |
Configuration options.
These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.
| Engine | Alternator | Phase | Voltage | Prime / PRP | Standby / ESP |
|---|---|---|---|---|---|
| 6M11G2D0/S | Stamford UCI274E1 | 3 | 400 V | 132 kVA | 145 kVA |
| 6M11G2D0/S | KWise C274G120 | 3 | 400 V | 133 kVA | 147 kVA |
Installation & enclosure
| Dimensions, weight and fuel tank | Confirmed with quotation and build drawing |
|---|
Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.
Fuel consumption
| 50% Load | 15.9 litres/hour |
|---|---|
| 75% Load | 23 litres/hour |
| 100% Load | 30.2 litres/hour |
| 110% Load | 33.1 litres/hour |
Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.