1,250 kVA class
Perkins generator
4008-30TAG3
A model-specific render and installation drawing will be supplied with the quotation.
Designed and manufacturedOpen set generator with a 4008-30TAG3 engine and Leroy Somer LSA50.2M6 reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.
Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.
Price and lead time confirmed with your quotation.
| GenPro model | GPS1250P |
|---|---|
| Engine brand / model | Perkins 4008-30TAG3 |
| Alternator | Leroy Somer LSA50.2M6 |
| Frequency | 50 Hz |
| Reference voltage | 400 V |
| Reference phase | 3 phase |
| Exact prime rating | 1125 kVA / 900 kW |
| Exact standby rating | 1250 kVA / 1000 kW |
| Aspiration | Turbocharged |
|---|---|
| Governor | Electronic |
| No. of Cylinders | 8 |
| Cylinder Arrangement | In Line |
| Displacement | 30.561L |
| Cooling Type | Liquid Cooled |
| Coolant Capacity | 140L |
| Oil Capacity | 153L |
| Type | Brushless |
| Poles | 4 |
| AVR Model | D350 |
| Voltage Regulation | 0.25% |
| Insulation Class | H |
| Excitation | Self Excited |
Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.
| Voltage | ESP kVA | ESP kW | PRP kVA | PRP kW |
|---|---|---|---|---|
| 400 V | 1250 kVA | 1000 kW | 1125 kVA | 900 kW |
These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.
| Engine | Alternator | Phase | Voltage | Prime / PRP | Standby / ESP |
|---|---|---|---|---|---|
| 4008-30TAG3 | Leroy Somer LSA50.2M6 | 3 | 400 V | 1125 kVA | 1250 kVA |
| 4008-30TAG3 | Stamford S6L1D-G41 | 3 | 400 V | 1122 kVA | 1248 kVA |
| 4008-30TAG3 | Stamford S6L1D-F41 | 3 | 400 V | 1130 kVA | 1230 kVA |
| 4008-30TAG3 | Leroy Somer LSA50.2M6 | 3 | 400 V | 1125 kVA | 1250 kVA |
| Dimensions (L × W × H) | 4430 × 2194 × 2270 mm |
|---|---|
| Reference weight | 7746.65 kg |
| Configuration market | Export |
Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.
| 50% Load | 120 litres/hour |
|---|---|
| 75% Load | 188 litres/hour |
| 100% Load | 244 litres/hour |
| 110% Load | 269 litres/hour |
Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.
4008-30TAG3
4012-46TWG2A
Tell us your load, site and application. We’ll help you choose the right configuration.