GENPRO / UK DESIGNED & MANUFACTURED GENERATORS+44 (0)121 517 0315
GENPRO / OPEN SETGPS1100CCummins · KTA38G5Build-specific image supplied with quotation

A model-specific render and installation drawing will be supplied with the quotation.

Cummins engine manufacturer logo
Designed and manufactured in the United KingdomDesigned and manufactured
in the United Kingdom
Cummins / Open set / 50 Hz

1,100 kVA class
Cummins diesel generator

GPS1100C

Open set generator with a KTA38G5 engine and Stamford S6L1D-E41 reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.

Prime / PRP1019 kVA815 kW
Standby / ESP1113 kVA890 kW

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

GenPro modelGPS1100C
Engine brand / modelCummins KTA38G5
AlternatorStamford S6L1D-E41
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating1019 kVA / 815 kW
Exact standby rating1113 kVA / 890 kW
AspirationTurbocharged
GovernorElectronic
No. of Cylinders12
Cylinder ArrangementAt Vee
Displacement37.8L
Cooling TypeLiquid Cooled
Coolant Capacity210L
Oil Capacity140L
TypeBrushless
Poles4
AVR ModelMX321
Voltage Regulation0.5%
Insulation ClassH
ExcitationPMG

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
380 V1100 kVA880 kW1000 kVA800 kW
400 V1113 kVA890 kW1019 kVA815 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
KTA38G5Stamford S6L1D-E413400 V1019 kVA1113 kVA
KTA38G5Leroy Somer TAL049E3400 V1000 kVA1100 kVA

Installation & enclosure

Reference weight8157.6 kg
Configuration marketExport

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load113 litres/hour
75% Load161 litres/hour
100% Load209 litres/hour
110% Load228 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.

Compare your options

Related generators.

Let’s specify your next generator.

Tell us your load, site and application. We’ll help you choose the right configuration.

Talk to GenPro