Technical specification.
| GenPro model | GPS110PS |
|---|---|
| Engine brand / model | Perkins 1104C-44TAG2 |
| Alternator | Stamford UCI274C1 |
| Frequency | 50 Hz |
| Reference voltage | 400 V |
| Reference phase | 3 phase |
| Exact prime rating | 100 kVA / 80 kW |
| Exact standby rating | 110 kVA / 88 kW |
| Aspiration | Turbocharged |
|---|---|
| Governor | Electronic |
| No. of Cylinders | 4 |
| Cylinder Arrangement | In Line |
| Displacement | 4.4L |
| Cooling Type | Liquid Cooled |
| Coolant Capacity | 12.6L |
| Oil Capacity | 8.0L |
| Type | Brushless |
| Poles | 4 |
| AVR Model | AS440 |
| Voltage Regulation | 1% |
| Insulation Class | H |
| Excitation | Self Excited |
Voltage-specific ratings
Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.
| Voltage | ESP kVA | ESP kW | PRP kVA | PRP kW |
|---|---|---|---|---|
| 190 V | 109 kVA | 87 kW | 100 kVA | 80 kW |
| 200 V | 110 kVA | 88 kW | 100 kVA | 80 kW |
| 208 V | 110 kVA | 88 kW | 100 kVA | 80 kW |
| 220 V | 109 kVA | 87 kW | 100 kVA | 80 kW |
| 230 V | 110 kVA | 88 kW | 100 kVA | 80 kW |
| 240 V | 110 kVA | 88 kW | 100 kVA | 80 kW |
| 380 V | 109 kVA | 87 kW | 100 kVA | 80 kW |
| 400 V | 110 kVA | 88 kW | 100 kVA | 80 kW |
| 415 V | 110 kVA | 88 kW | 100 kVA | 80 kW |
Configuration options.
These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.
| Engine | Alternator | Phase | Voltage | Prime / PRP | Standby / ESP |
|---|---|---|---|---|---|
| 1104C-44TAG2 | Stamford UCI274C1 | 3 | 400 V | 100 kVA | 110 kVA |
| 1104C-44TAG2 | Leroy Somer TAL044D | 3 | 400 V | 100 kVA | 110 kVA |
Installation & enclosure
| Dimensions (L × W × H) | 2286 × 1104 × 1620 mm |
|---|---|
| Reference weight | 1467 kg |
| Reference fuel tank | 210 litres |
| Configuration market | UK/EU |
| Manufacturer noise reference at 7 m | 76 dB(A) |
Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.
Fuel consumption
| 50% Load | 11.8 litres/hour |
|---|---|
| 75% Load | 17.1 litres/hour |
| 100% Load | 22.6 litres/hour |
| 110% Load | 24.9 litres/hour |
Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.